ELC500 Control unit
171
Data Registerd for Data Collection
9.3
The below data registers are used for data collection.
Using DT0 to 15999, it display current value monitor of ELC500 logging data.
File No.
Registration
No.
Register starting No.
(
2 words
)
Register starting No.
(
4 words
)
DT range
0
1
DT0
DT0
DT0 to DT999
2
DT2
DT4
:
:
:
127
DT252
DT504
128
DT254
DT508
1
DT1000 to DT1999
2
DT2000 to DT2999
3
DT3000 to DT3999
4
DT4000 to DT4999
5
DT5000 to DT5999
6
DT6000 to DT6999
7
DT7000 to DT7999
8
DT8000 to DT8999
9
DT9000 to DT9999
10
DT10000 to DT10999
11
DT11000 to DT11999
12
DT12000 to DT12999
13
DT13000 to DT13999
14
DT14000 to DT14999
15
DT15000 to DT15999
Note
- One file contains 128 registers. The others are reserved registers.
- 2-words or 4-words data register is occupied regardless the logging device type.
You can set occupied word at ELC basic setup for each file No.
- It saves ‘0’ during ELC500 set to STOP/PROG mode.