ELC500 Control unit
92
Item
Description
(a)
Name
Set name for logging device.
<Set range> 32-letter or less
(b)
Communication I/F *1
Set communication I/F that is connected the devices used
to collect relay data.
<Initial> Main unit
<Set range> Main unit/COM0 /COM1 /COM2 /Ethernet
(c)
Connection device *2
Set device to collect logging data.
(d)
Data type
Set data type to collect data.
<Initial> register
<Set range> register/ relay
(e)
Device
*3
Data type:
Register *4
Set register data to collect.
<Initial> Device: DT 0
<Set range> DT /LD /FL /WX /WY /WR /WL /SV / EV
Number: 0 to 99999
Data type:
Relay *4
Set relay data to collect.
<Initial> Device R 0
<Set range> R /X /Y /L /T /C
Number: 0 to 99999F
(f)
Data style *5
Set data style of register data to collect.
<Initial> DEC1W(Unsigned)
<Set range>
DEC1W, DEC1W(Unsigned)
DEC2W, DEC2W(Unsigned)
DEC4W, DEC4W(Unsigned)
HEX (4-digit / 8-digit / 16-digit),
single precision real number,
double-precision real number
(g)
Reading order *5 *6 *7
Set reading order when it saves collecting data to register
by MODBUS RTU or MODBUS TCP.
<Initial> Low word – High word
<Set range> Low word – High word / High word - Low word
(h)
Logging contents *8
Set logging data contents.
Inst. value: Collecting value is saved without change.
Diff. value: Differential value from the previous collected
value is saved.
<Initial> Inst. value
<Set range> Inst. value / Diff. value
(i)
Offset value *5 *9 *10
Set offset value. (add value to collected value)
<Initial> 0
<Set range> -32768 to 32767
(j)
Upper limit value *11
Set upper limit value (max value of collected value)
<Initial>0
<Set range>1 to 65535 / 1 to 4294967295 /
1 to 18446744073709551615
(k)
Multiplier *5*10
Set conversion value of collecting data.
<Initial> 1
<Set range> 0.0001 to 9999.9999