ELC500 Control unit
107
■
Setup for Fixed-time demand (Average power method)
Item
Description
(a)
Name
Set name for demand control pattern
<Set range> 32-letter or less
(b)
Trigger
Set trigger from the registered trigger.
It works alarm function at this trigger, it works alarm function.
(c)
Period
Set demand period.
<Initial>30 min
<Set range>15 / 30 / 60
(d)
Alarm mask time
Set alarm mask time.
<Initial> 0 min
<Set range> 0 to 10
(e)
Control demand value
Set control demand value
<Initial> 0 kW
<Set range> 0 to 999999999999999
(f)
Limit control demand
value
Set limit control demand value
<Initial>0 kW
<Set range> 0 to 999999999999999 kW
(g)
Target demand value
Set target demand value
<Initial>0 kW
<Set range>0
~
999999999999999 kW
* Set each value as the followings.
Target demand value
≧
Limit control demand value
≧
Control demand value
If it doesn’t meet this condition, error message will be appeared.
(a)
(b)
(c)
(d)
(e)
(f)
(g)