109
8.3 Output Specifications
Number of output point
2 points *Insulate between output terminals
Insulation method
PhotoMOS relay
Output type
1a
Output capacity
100mA, 30V AC/DC
Output mode (OUT1/OUT2)
・
Pulse by integral power
・
Output by alarm or events
(set with setting mode)
Pulse by
integral power
Pulse width
Approx. 100ms
Pulse output
unit
0.0001kWh/ 0.001kWh/ 0.01kWh/ 0.1kWh/
1kWh/ 10kWh/ 100kWh
Alarm
Event
Type
Stand-by alarm/ Under voltage alarm/ Over voltage alarm/
Power interruption alarm/ Under current alarm/
Over current alarm/ Active power alarm/ Reactive power alarm/
Apparent power alarm/ PF alarm/ Over frequency alarm/
Under frequency alarm/ Voltage harmonics alarm/
Current harmonics alarm/ Voltage THD alarm/
Current THD alarm/ Unbalanced voltage alarm/
Unbalanced current alarm/
Power demand alarm/ Current demand alarm/ counter output/
level output (external control)
Alarm reset
Self-reset (according to the setting) / Manual-reset
Protection element
Varistor *1
*1 Varistor is mounted internal as a protection element.
Install a protective device in case of using at the place where it effects by surge.
<Internal output circuit>
How to calculate
Unit for pulse output
>
(Max. measurement power [kW]
)/
(3600[s]
×
1 [pulse/s])
Note
(1) Improper unit setting may cause miss counting.
(2) If the OFF time is too short, there is a possibility of counting errors.