8.4 Input Specifications
Number of input point
2 points
*Not insulate between input terminals (COM is common.)
Insulation method
Designated insulation for input (insulate to the other functions)
Input method
Contact/ non-voltage a contact or open-collector
Input signal
Non-voltage
・
Impedance; Max. 1kΩ
(when short-circuit current: Max. 10mA)
・
Residual voltage when shorted; Max. 3V
・
Impedance when open: Min. 100kΩ
Input mode
IN1
Pulse input or synchronized with input from outer device
IN2
Pulse input
Max. counting speed
IN1
30Hz (when pulse input)
IN2
2000Hz / 30Hz
Min. input signal
width
IN1
16.7m ON:OFF ratio
=
1:1
IN2
0.25ms (when 2000Hz is set) / 16.7ms(when 30Hz is set)
ON:OFF ratio
=
1:1
Pre-scale
Decimal point
Under 3-digit
Range
0.001 to 100.000 (set with setting mode)
Output mode
(when pulse output is selected)
HOLD
Protective elements
Zener diode
<Internal input circuit>
R: resister
C: capacitor