40
Over frequency alarm threshold (OUT1 OUT2)
* It is only when [AL-oF] is selected for unit for pulse output.
Set a value of frequency to use for alarm output.
Press <ITEM/
△
>, <SHIFT/
▽
> to set.
[Set range] 0.00 to 100.00 [Hz] (initial:100.00)
Increase
decrease
Over frequency alarm OFF threshold (OUT1 OUT2)
* It is only when [AL-oF] is selected for unit for pulse output.
Set a value of frequency to clear the alarm output.
Press <ITEM/
△
>, <SHIFT/
▽
> to set.
[Set range] 0.00 to 100.00 [Hz] (initial:100.00)
Increase
decrease
Under frequency alarm threshold (OUT1 OUT2)
* It is only when [AL-UF] is selected for unit for pulse output.
Set a value of frequency to use for alarm output.
Press <ITEM/
△
>, <SHIFT/
▽
> to set.
[Set range] 0.00 to 100.00 [Hz] (initial0.00)
Increase
decrease
Under frequency alarm OFF threshold (OUT1 OUT2)
* It is only when [AL-UF] is selected for unit for pulse output.
Set a value of frequency to clear the alarm output.
Press <ITEM/
△
>, <SHIFT/
▽
> to set.
[Set range] 0.00 to 100.00 [Hz] (initial0.00)
Increase
decrease