28
Under voltage / Under voltage 2
Set a ratio of voltage for rated voltage used for threshold to judge under voltage and to clear the
under voltage.
At [under volt] window set a ratio of voltage to judge under voltage.
Press <ITEM/
△
>, <SHIFT/
▽
> to set the ratio.
[Set range] 5.0 to 100.0% (initial:95.0)
Increase
decrease
Press <SET>, and [under volt 2] is displayed. At this window, set a ratio of voltage to clear under
voltage.
Press <ITEM/
△
>, <SHIFT/
▽
> to set the ratio.
[Set range] 5.0 to 100.0% (initial:95.0)
Increase
decrease
ex.) Settings; [under volt] 95.0%, [under volt 2]
When measured voltage is under 95.0%, it judges under voltage and output alarm.
During output the alarm, if the measured voltage becomes over 100.0%, it will clear the alarm.
Over current / Over current 2
Set a ratio of current for rated current used for threshold to judge over current and to clear the
over current.
At [over curr] window set a ratio of current to judge over current.
Press <ITEM/
△
>, <SHIFT/
▽
> to set the ratio.
[Set range] 0.1 to 120.0% (initial:100.0)
Increase
decrease
Press <SET>, and [over curr 2] is displayed. At this window, set a ratio of current to clear over current.
Press <ITEM/
△
>, <SHIFT/
▽
> to set the ratio.
[Set range] 0.1 to 120.0% (initial:100.0)
Increase
decrease
ex.) Settings; [over curr] 120.0%, [over curr 2] 105.0%
When measured current is over 120.0%, it judges over current and output alarm.
During output the alarm, if the measured current becomes fewer than 105.0%, it will clear the
alarm.