48
Transmission format
*Select [8b-E] when [645] is set for the protocol.
Select serial communication (RS485) transmission format (Data length, Parity).
Define the transmission format according to the master’s (PLC etc.).
Press <ITEM/
△
>, <SHIFT/
▽
> to select.
[Set list] 8b-o (8bit odd), 8b-n (8bit none), 8b-E (8bit even) (initial: 8b-o)
Stop bit
*Select [1] when [645] is set for the protocol.
Select serial communication (RS485) stop bit.
Press <ITEM/
△
>, <SHIFT/
▽
> to select.
[Set list] 1, 2 (initial: 1)
Response time
*Select 50 or more when [645] is set for the protocol.
Set serial communication (RS485) response time of main unit.
When command is received, it sends response after setting response time passes.
Press <ITEM/
△
>, <SHIFT/
▽
> to set.
[Set range] 1 to 99 ms (initial: 5)
increase
decrease
* If Data Logger Unit (DLU) or Data Logger Light (DLL) is used as a master, set the response time to
5ms or more because DLU or DLL send the response after 1.1ms or less from receive a command
when transmission speed is set to 19200bps.