OPERATION COMMAND SELECT(Parameter P08)
Used to select whether to carry out start/stop and forward/reverse with the
operation panel (panel), with signals input from external devices or with
communication command.
Data
setting
value
Panel
external
control
0
Panel
reset
function
Panel
Provided
Forward run:
Ʒ
RUN, Reverse run:
ͩ
RUN, Stop: STOP
1
Start: RUN, Stop: STOP, Forward/reverse: set in dr mode
External
control
1
2
OPEN signal (ON: Forward /OFF: Stop)
CLOSE signal (ON: Reverse /OFF: Stop)
8
Common terminal
2
Provided
Provided
3
Operation method and control terminal connection diagram
Comm-
unication
Make the operation command input by communication valid.
0
Output frequency (Hz)
Output frequency (Hz)
Output frequency (Hz)
100
[ParameterP06
˙
1
@
[ParameterP06
˙
2
@
[ParameterP06
˙
3
@
Boost
level
Boost
level
Boost
level
䋨䋦䋩
50
0
100
䋨䋦䋩
50
90
60
25
0
100
䋨䋦䋩
50
60
15
䃂
Panel reset function
䊶
When a fault trip occurs, the state can be reset with the "STOP button" on the operation panel.
(This function is called" Panel reset function".)
䃂
Panel STOP function
䊶
When setting external control (Parameter P08="2"), the operation may stop with
"STOP button" on operation panel. At this time, the panel displays " " .
(This function is called as "Panel STOP function".)
㵰
䊶
When the panel displays " ", repress "STOP button" to release the stop state.
In this case , if the operation signal of control terminal is ON, the inverter begins to
carry out operation.
Depending on the start mode function setting, if the fault trip is reset
or the stop state is released with panel STOP function" with run signal
being input, the inverter may restart suddenly.
(Perform the operation after ensuring personal safety.)
Failure to do so could lead to injury.
43
!
Caution: