65
Operation is carried out as fault CLOSE command signal.
2
When CLOSE command signal is ON, and safety sensor
signal is ON, fault CLOSE operation iscarriedout.
1
When safety sensor signal is ON, fault OPEN operation is
carried out.
0
Functions
Setting data
value
Function select of safety sensor signal in control input terminal No.5 may be carried out.
䇼
When data value is set to be 0
䇽
After safety sensor signal is ON, OPEN operation is forced to becarried out by
the door in virtue of obstacle detect function. Response time of safety sensor
signal may be set with Parameter P44.
䇼
When data value is set to be 1
䇽
In the state that CLOSE command signal is ON, after safety sensor signal is ON,
fault CLOSE operation is carried out by the door. In case of no CLOSE command
signal, no fault CLOSE operation will be carried out even if safety sensor signal is ON.
䇼
When data value is set to be 2
䇽
Control input terminal No.5 serves as fault CLOSE command signal.
When fault CLOSE command signal is ON, fault CLOSE operation will be carried
out. Only with fault CLOSE command, fault CLOSE operation will be carried out.
Priority order of the three run commands (OPEN command, CLOSE command
and fault CLOSE command) is as follows. When all of the three signals are ON
simultaneously, note that operation will becarried out according to the following
priority order.
䋾
䋾
(Note) When fault CLOSE operation is being carried out in CLOSE operation
region, and fault CLOSE command signal is OFF (OPEN command and CLOSE
command are both OFF), note that operation will be different due to setting value
of Parameter P75 ( stop select in OPEN/CLOSE operation).
OPEN
command
fault
CLOSE
command
CLOSE
command
About fault CLOSE operation
䊶
In the event that signal input in control input terminal No.5 (parameter 80 is
䇸
1
䇹
or
䇸
2
䇹
)
is ON, fault CLOSE operation is carried out according to frequency and acceleration /
deceleration time in fault CLOSE operation.
䊶
Hold operation is identical to CLOSE hold operation.
䊶
In fault CLOSE operation, OPEN operation is carried out when OPEN command is ON.
䊶
In fault CLOSE operation, obstacle detect (time, slip and current) is still effective.
䊶
Obstacle detect conducted in fault CLOSE operation, its setting value is that of
parameter 81: forced OPEN operation judgment time in fault CLOSEoperation.
䊶
When RY1
䊶
2
䊶
3function select (P48
䌾
P50
䋩䋽
6
䇮
r6, , obstacle detect signal is set
to be ON in fault CLOSE operation.
Parameter P80:
Safety sensor function select