Note1) This is the min. time for operation at the rated output current.
Note2) This is the min. time.
Even if the power failure time is relatively long(approx. 1 min), the inverter may
restart after the power is restored.
Note3) The wait time can be set between 0.1 to 100s. with parameter P25.
WAIT TIME (Parameter P25)
Used to set the wait time for the start mode, the restart function after an
instantaneous failure and retry functions
Data setting range(s) 0.1 to 100
䂹
If an inverter fault trip occurs, the retry function will automatically reset the
fault and will restart (run) operation after the wait time has elapsed.
Use this function to continue operation.
䊶
Select the "retry function validity" and the details of the fault for carrying
out retry with parameter P26.
䊶
Set the "retry times" with parameter p27.
䊶
The time interval for retrying is set with parameter P25(wait time).
䊶
The fault warning signal will not be output during retry. If a fault occurs
even when the set number of retries has been carried out, a fault warning
signal will be issued.
䊶
If a fault not selected occurs during retry, a fault warning signal will be
output, and the counted retry times will be cleared.
䊶
The counted retry times will be cleared when the power is turned OFF.
䊶
If a fault dose not occur for 5 or more minutes, the counted retry times
will be cleared.
RETRY FUNCTION and RETRY TIME(Parameter P26 and P27)
When the retry function is used, the inverter may automatically
start(restart). Keep out of the machine.
(Secure personal safety before using this function. Failure to do
so could lead to injury.)
51