Data setting range (s)
ARRIVAL SW FAULT DETECT TIME(Parameter P47)
When door position data is arrival hold area without arrival signal, or OPEN/
CLOSE Arrival signal are both ON, arrival SW fault is detected.
The fault detection time for OPEN/CLOSE Arrival signal can be set with
parameter P47.
0
g
0.1 to 10 ("0" indicates that there is no arrival SW fault detect function.)
Note) The factory data is set to "0" (no arrival SW fault detect function).
RY 1, 2,3 FUNCTION SELECT (Parameter P48,49 and 50)
Used to set the functions of the relay output ( control terminals A, B and C).
[Parameter P48: Function selection for RY1]
[Parameter P49: Function selection for RY2]
[Parameter P50: Function selection for RY3]
䊶
Energize in on-state: The relay is turned ON when the coil is excited.
( The signal on-state= Across terminals A-C: ON, across terminals B-C: OFF)
Non energize in on-state: The relay is turned ON when the coil is not excited.
( The signal on-state= Across terminals A-C: OFF, across terminals B-C: ON)
Setting data
Energize in
on-state
Non
energize in
on-state
Function
Conditions for relay to turn ON
0
r0
Run signal
ON when run signal is ON or during inverter output.
1
r1
Reverse run
signal
ON when the inverter is running in reverse.
2
r2
Arrival signal
ON when the output frequency is within the setting
frequency
f
2Hz
3
r3
Overload alarm
ON when the output current is 140%of the reference
current (3.6A) or higher or when the electronic thermal
level is reached.
4
r4
OPEN arrival
signal
The detection position of the encoder is in ON hold
area or OPEN arrival signal is turned ON.
5
r5
CLOSE arrival
signal
The detection position of the encoder is in OFF
hold area or CLOSE arrival signal is turned ON.
6
r6
Obstacle
detection signal ON when fault ON operation of obstacle detection
7
r7
Fault alarm
ON when the inverter is in the fault trip state.