RIDE-THROUGH RESTART(Parameter P24)
Depending on the restart setting after an instantaneous power failure, the
inverter may automatically start(restart) if the power is restored after a power
failure. Keep out of the machine.
(Operate the inverter after ensuring personal safety. Failure to do so could
lead to injury.)
Used to select the restart mode after an instantaneous power failure occurs,
according to the load conditions and system. A wait timer function is built-in.
Data
setting
value
0
Operation
continues
䊶
The LU trips, and the inverter operates according to the start
mode setting.
䊶
"LU" will be displayed, and a fault warning signal will be output.
Min. 15ms or
less (Note 1)
䊶
Restart from 0Hz after the wait time has elapsed.
䊶
"LU" will be displayed, but a fault warning signal
will not be output.
1
2
Inverter operation in regard to instantaneous power failure time
Exceeding min.15ms
(Note 1)
Exceeding min.
100ms (Note 2)
Min. 100ms
(Note 2)
䊶
After the wait time has elapsed, the inverter restarts
at the frequency applied before the ride-through
restart occurred.
䊶
"LU" will be displayed, but a fault warning signal
will not be output.
Operation
takes place
according to
the details
set in the
start mode.
[When voltage drop time is more than 15ms but less than 100ms]
䊶
Data setting value
"0"(No restart after
an instantaneous
failure)
Output
frequency
Output
frequency
Output
frequency
Power
supply
Voltage drop time
LU level
䊶
Data setting value
"1"(0Hz restart)
䊶
Data setting value
"2"(continue to restart)
Operates according to the start mode
setting details
Wait time
(parameter P25)
Current limit function
LU
trip
LU
trip
LU
trip
0
0
0
0
50
!
Caution