LMX SERIES™ OPERATION MANUAL
SECTION 8:
Entire Contents Copyright
2018 by Pacific Power Source, Inc. (PPS) • All Rights Reserved • No reproduction without written authorization from PPS.
LMX Series Power Source Operation Manual
Page 246 of 463
Command Syntax
[SOURce:]CONFIG:HFreq <b>
Description
This command enables high-frequency output current protection
extension mode. In this mode, the protection for high frequency
content at the output of the power source is held off for up to 2
seconds to allow short time events to ride through without tripping
the normal protection mode.
Note:
Available in units with Firmware revision 1.6.6 or higher.
Parameters
< 0 | OFF | 1 | ON >
( 0 = Off, 1 = On)
Parameter Format
<b>
Example
SOUR:CONFIG:HF 1
Query Format
[SOURce:]CONFIG:HFreq?
Returned Data Format
<b>
Query Example
CONFIG:HF?
1