3.2 

Selecting menu points and adjusting values 

During normal operation of the controller, the display is in the Status menu. If no 
button is pressed for a few seconds, the display illumination goes out.
Press any key to reactivate the display illumination.

 

Î

In order to scroll through a menu or to adjust a value, press either buttons 

 

and 

 or buttons 

 and 

.

 

Î

To open a sub-menu or to confirm a value, press button 

.

 

Î

To re-enter the status menu, press button 

 – unconfirmed adjustments will 

not be saved.

 

Î

To enter the previous menu, press button 

 – unconfirmed adjustments will 

not be saved.

Use the buttons 

 and 

 for scrolling through the status menu.

With the parameters Mixer and HC pump in the status menu of the heating 
circuits
, a shortcut to the Manual mode is possible, for example, for carrying 
out a mixer test. 

 

Î

In order to enter the Manual mode, press button 

.

 

Î

In order to get back to the status menu of the heating circuit, press button 

.

If no button has been pressed within a couple of minutes, the adjustment is can-
celled and the previous value is retained.

Note:
After having carried out the adjustments, the controller has to be kept 
switched-on for at least 2 min for storing the adjustments.

Chimney  sweeper / screed  drying
The chimney sweeper or screed drying function can be triggered with the button 

. The chimney sweeper function is activated by default. In order to activate the 

screed drying function, the chimney sweeper function must be deactivated in all 
heating circuits (see page 26).

 

Î

In order to trigger the chimney sweeper or screed drying function, press and 
hold down button 

 for 5 s.

Operation and function

3.1 

Buttons

The controller is operated via the 7 buttons next to the display. They have the 
following functions:
Button 

  -  scrolling upwards

Button 

  -  scrolling downwards 

Button 

  -  increasing adjustment values

Button 

  -  reducing adjustment values

Button 

  -  confirming 

Button 

  -  entering the status menu / chimney sweeper mode or screed drying 

mode (system-dependent)

Button 

  -  escape button for changing into the previous menu

1

2

4

6

3

5

7

Operating control LED (in the directional pad)
Green:  

Everything OK

Red:  

Error / cancellation screed drying

Red flashing: 

Sensor fault, initialisation

Green flashing:  Manual mode

Summary of Contents for Regtronic RH HT

Page 1: ...lves controls systems Regtronic RH HT Installation and operating instructions for the specialised installer EN Please read this manual carefully to get the best performance from this unit Please keep...

Page 2: ...exclusively addressed to authorised skilled personnel Only qualified electricians should carry out electrical works Initial commissioning must be effected by the system installer or qualified person...

Page 3: ...l connection 5 2 3 Data communication Bus 7 2 4 SD card slot 7 3 Operation and function 8 3 1 Buttons 8 3 2 Selecting menu points and adjusting values 8 4 Commissioning 13 4 1 Schemes with basic setti...

Page 4: ...relays 1 potential free relay 2 PWM outputs 24V output PWM frequency 1000 Hz PWM voltage 10 5V Switching capacity 1 1 A 240V semiconductor relay 4 2 A 240V electromechanical relay 4 1 A 240V potentia...

Page 5: ...l Drill and fasten the enclosed wall plug and screw leaving the head protruding Hang the housing from the upper fastening point and mark the lower fasten ing points centres 150 mm Insert lower wall pl...

Page 6: ...l S9 can be used as an impulse input for an impulse flow rate sensor or as an input for a flow switch An impulse flow rate sensor can be connected to the terminals S9 V40 and GND either polarity Conne...

Page 7: ...isted in the following e g Grundfos Magna 3 Wilo Stratos 50 1 12 Wilo Stratos 40 1 8 KSB Calio 30 120 2 3 Data communication Bus The controller is equipped with the S Bus for data transfer with extern...

Page 8: ...a couple of minutes the adjustment is can celled and the previous value is retained Note After having carried out the adjustments the controller has to be kept switched on for at least 2 min for stor...

Page 9: ...ar indicates the current adjustment By pressing buttons or the upper slide bar can be moved to the left or to the right Only after the adjustment has been confirmed by pressing button will the number...

Page 10: ...n for the follow ing steps The last menu item after the list of days is Contin ue If Continue is selected the timer menu opens in which the time frames can be adjusted Adding a time frame In order to...

Page 11: ...e to be copied All time frames adjusted for the selected day or com bination will be copied If the time frames copied are not changed the day or combination will be added to the combination from which...

Page 12: ...on proceed as follows Select the desired day or combination The selected day or combination will disappear from the list all its time frames will be deleted In order to reset the whole timer proceed a...

Page 13: ...r through the most important adjustment channels needed for operating the system Commissioning menu The commissioning menu consists of the channels described in the following In order to make an adjus...

Page 14: ...g can be changed any time in the corresponding adjustment channel Additional functions and options can also be activated or deactivated Set the code to the customer code before handing over the contro...

Page 15: ...rcuits can be activated and adjusted For the heating part of the arrangement optional functions can be selected acti vated and adjusted DHW heating Circulation Thermal disinfection Heating circuits an...

Page 16: ...values selectable are variable depending on ad justments already made The figure only shows an exemplary excerpt of the com plete menu in order to visualise the menu structure Basic settings Language...

Page 17: ...ting circuit as well as the optionally activated DHW heating and circulation are switched off Holiday Constant heating mode within an adjustable time frame with the adjust ed night correction and the...

Page 18: ...ensor line is indicated as Sensor fault A pre cise error code can be found in the Status Meas Balance values menu 6 Heating In this menu all adjustments for the heating part of the arrangement or for...

Page 19: ...60 s TStart up Boiler start up temperature 10 90 C 60 C Overrun Pump overrun No Time Temperature No Overrun time Overrun time 0 300 s 60 s TOverrun Remaining boiler temperature 10 90 C 50 C Sensor Bo...

Page 20: ...e values Spannungssignal inV 10V Volt 2 Volt 1 0V Tmin TSoll 1 TSoll 2 Tmax Kesselsolltemperatur in C Set boiler temperature in C Voltage signal inV By means of the adjustment channels Tmax and Tmin t...

Page 21: ...r the first time the first heating circuit is allocated to the controller The operating mode of the first heating circuit also applies to all further heating circuits if they are linked In the heating...

Page 22: ...5 K Fur thermore the heating circuit can be switched off or a rapid heating can be carried out by means of the remote control Heating circuit switched off means that the heating circuit pump is switch...

Page 23: ...oom factor 10 Room control For the Room control with room factor 10 the adjustment of all room ther mostats activated will be considered The controller will calculate the average value of the deviatio...

Page 24: ...n be used for adjusting the time frames for day operation Summer mode The automatic summer mode becomes active when the outdoor temperature exceeds the adjusted summer temperature TSummer This can be...

Page 25: ...rovide direct backup heating without a store Separate relays can be allocated to a demand and to a boiler loading pump free re lays or shared relays demand 1 2 or pump 1 2 respectively If shared relay...

Page 26: ...room control unit only The controller menu only allows the activation of the operating mode Holiday Remote access with the app In addition to the wireline possibilities of remote access an app can be...

Page 27: ...teresis RTH hysteresis 0 5 20 0 K 0 5 K Timer RTH timer Yes No No Correction Correction 1 20K 3K Relay RTH relay selection system dependent system dependent RTH Room thermostat Activated Deactivated A...

Page 28: ...t to standby by using the Activated item If the button is pressed and held down for at least 5 s the screed drying pro gramme will start The message Screed drying will be indicated on the display and...

Page 29: ...ated in all heating circuits Note Make sure the heating circuits are supplied with heat from a heat source backup heating Note If an SD card has been inserted into the slot a screed protocol will be g...

Page 30: ...g as a solid fuel boiler is switched on which has previously been activated in the Arrangement Optional functions menu When a function has been selected and adjusted it will appear in the Opt func tio...

Page 31: ...function DHW heating Adjustment channel Description Adjustment range selection Factory setting DHW heating DHW heating system dependent system dependent Mode Mode Therm Zone Therm Sensor 1 Reference...

Page 32: ...The activation of the backup heating is then delayed until that starting time after the monitoring period has ended If the monitoring period ends for example at 12 00 o clock and the starting time ha...

Page 33: ...witch es on when the temperature falls below the adjusted switch on temperature If the temperature exceeds the switch off temperature the relay switches off Relay Sensor Circulation Timer The relay is...

Page 34: ...the transmission station to the temperature required by the loads e g heating circuit If the function is activated the transmis sion station is available as the virtual relay Tr st in the relay alloc...

Page 35: ...on The menu item Relay selec is available in all optional functions Therefore it will not be explained in the individual function descriptions With this menu item a relay can be allocated to the funct...

Page 36: ...on system dependent system dependent Delay Delay option Yes No No Duration Delay time 1 30 min 1 min Overrun Overrun option Yes No No Duration Overrun time 1 30 min 1 min Inverted Inverted switching o...

Page 37: ...switch on and switch off conditions 2 sensors are used The switch on and switch off temperatures Ton and Toff are used as reference parameters If the measured temperatures at both allocated sensors f...

Page 38: ...located sensors has not fallen below the switch off temperature difference the temperature at the heat source sensor has exceeded the minimum temperature the temperature at the heat sink sensor has fa...

Page 39: ...tore Store sensor selection system dependent system dependent Adjustment channel Description Adjustment range selection Factory setting DTon Switch on temperature difference 2 0 30 0 K 6 0 K DToff Swi...

Page 40: ...the function block is switched on as soon as the adjust ed switch on temperature difference Th x on is reached It is switched off as soon as the adjusted switch off temperature difference Th x off is...

Page 41: ...stem dependent Relay Reference relay 2 selection system dependent system dependent Relay Reference relay 3 selection system dependent system dependent Funct Activation Deactivation Activated Deactivat...

Page 42: ...never the allo cated relay is active In the adjustment channel Fluid type the heat transfer fluid must be selected If either propylene glycol or ethylene glycol is selected the adjustment channel Rati...

Page 43: ...ettings All adjustments that have previously been made will be lost For this reason a security enquiry will appear after the reset function has been selected Only confirm the security enquiry if you a...

Page 44: ...ng int Logging interval 00 01 20 00 mm ss 01 00 Logging type Logging type Cyclic Linear Cyclic 10 SD card The controller is equipped with an SD card slot for SD memory cards With an SD card the follow...

Page 45: ...Relay active at 100 speed manual mode Auto Relay is in automatic mode Note After service and maintenance work the relay mode must be set back to Auto Normal operation is not possible in manual mode M...

Page 46: ...ent range selection Factory setting Module 1 5 Registering external modules 13 2 Inputs In this sub menu the type of the sensor connected can be adjusted for each indi vidual input The following types...

Page 47: ...200 l min 5 100 l min 2 40 l min 2 40 l min fast 1 20 l min 1 12 l min 1 12 l min For the Inputs Gd1 and Gd2 the following sensor combinations are possible 1 x RPD 1 xVFD 2 xVFD but with different me...

Page 48: ...Sensor 0 10V PWM A B RPD N Isolate mains before removing cover Vor ffnen Ger t spannungslos schalten Use ground common terminal block Masse Sammelklemme benutzen Use neutral conductor common terminal...

Page 49: ...is removed The fuse can then be replaced Press button Display illuminated no yes Controller has been in standby everything o k Check the power supply of the controller Is it disconnected no yes C F P...

Page 50: ...losses now no yes o k Controller might be defective replace it Is the pump stuck Turn the pump shaft using a screwdriver now passable Pump is defective replace it yes no Does the DHW circulation run...

Page 51: ...ng pumps Grundfos UPM3 15 70 130 Solar PM2 15 85 130 Wilo Yonos Para ST15 7 PWM2 Yonos Para ST25 7 130 PWM2 Yonos Para ST25 7 180 PWM2 Stratos Para 15 1 11 5 Stratos Tec 15 6 130 PWM Stratos Tec 15 7...

Page 52: ...DHW priority 25 E Error relay 41 F Firmware updates 44 Function block 40 Fuse replacing of 49 H Heat exchange 38 Heating circuit mixer 21 Heating circuit pump 21 Heating curve 21 Heat quantity measur...

Page 53: ...thermostat 23 S Scheme 14 Screed drying 28 Sensor fault error message 18 Sensor offset 46 Set flow temperature 21 Shared relays 18 Solid fuel boiler 39 Starting time 25 Start temperature 28 Start up...

Page 54: ...en 54...

Page 55: ...en 55...

Page 56: ...notice 139102582 11 2020 OVENTROP GmbH Co KG Paul Oventrop Stra e 1 D 59939 Olsberg Telephone 49 0 296282 0 Fax 49 0 296282 400 E Mail mail oventrop de Internet www oventrop com For an overview of ou...

Reviews: