Heat exchange
Arrangement / Opt. functions / Add new function / Heat exchange
Adjustment
channel
Description
Adjustment range /
selection
Factory setting
Relay
Relay selection
system dependent
system dependent
Sen. Source Heat source sensor selection
system dependent
system dependent
Sen. Sink
Heat sink sensor selection
system dependent
system dependent
D
Ton
Switch-on temperature difference 1.0 … 30.0 K
6.0 K
D
Toff
Switch-off temperature difference 0.5 … 29.5 K
4.0 K
D
Tset
Set temperature difference
1.5 … 40.0 K
10.0 K
Rise
Rise
1.0 … 20.0 K
2.0 K
Min speed
Minimum speed
20 … 100 %
100 %
Tmax
Maximum temperature of the
store to be loaded
10 … 95 °C
60 °C
Tmin
Minimum temperature of the
store to be loaded
10 … 95 °C
10 °C
Timer
Timer
-
-
Day
selection
Day selection
All days, Mon-
day … Sunday, Continue
-
Timer
Time frame adjustment
00:00 … 23:45
-
Funct.
Activation / Deactivation
Activated / Deactivated Activated
The Heat exchange function can be used for transferring heat from a heat
source to a heat sink.
The allocated relay is energised when all switch-on conditions are fulfilled:
• the temperature difference between the allocated sensors has exceeded the
switch-on temperature difference
• the temperature difference between the allocated sensors has not fallen below
the switch-off temperature difference
• the temperature at the heat source sensor has exceeded the minimum temperature
• the temperature at the heat sink sensor has fallen below the maximum temperature
• one of the adjusted time frames is active (if the Timer option is selected)
Speed control is deactivated by default. In order to activate speed control, reduce
the minimum pump speed.
When the Set temperature difference is exceeded, pump speed control
starts. If the temperature difference increases by the adjustable Rise value, the
pump speed increases by 10 % respectively.
Note:
For information on timer adjustment see page 10.
Relay
Sensor Sink
Sensor Source
Return preheating
Arrangement / Opt. functions / Add new function / Ret. preheat.
Adjustment
channel
Description
Adjustment range /
selection
Factory setting
Relay
Relay selection
system dependent
system dependent
Sen. HS
Heat source sensor selection
system dependent
system dependent
Sen. Return Return sensor selection
system dependent
system dependent
D
Ton
Switch-on temperature difference 2.0 … 30.0 K
6.0 K
D
Toff
Switch-off temperature difference 1.0 … 29.0 K
4.0 K
Summer off Summer switch-off option
Yes, No
No
Sensor
Outdoor sensor selection
system dependent
system dependent
Toff
Switch-off temperature
10 … 60 °C
20 °C
Funct.
Activation / Deactivation
Activated / Deactivated Activated
The Return preheating function can be used for transferring heat from a heat
source to the heating circuit return.