Installation
19
Commissioning
Settings
Tr
oubleshooting
Data comm
unication
en
Heating / Shared rel.
Adjustment
channel
Description
Adjustment range /
selection
Factory setting
Dem. 1 (2)
Demand 1 (2)
Activated, Deactivated Deactivated
Relay
Relay option
Yes, No
No
Relay
Relay sub-menu
-
-
Output
Output selection
system dependent
R5
Boiler pr. min Option for boiler protection min Yes, No
No
Tmin
Minimum boiler temperature
10 … 90 °C
55 °C
Boiler pr. max Option for boiler protection max Yes, No
No
Tmax
Maximum boiler temperature
20 … 95 °C
90 °C
Sensor Boiler Boiler sensor selection
system dependent
S4
0-10 V
0-10 V option
Yes, No
No
0-10 V
0-10 V sub-menu
-
-
Output
Output selection
-, A, B
D
Tset 1
Lower boiler temperature
10 … 90 °C
10 °C
Volt 1
Lower voltage
0.0 … 10.0 V
1.0 V
Tset 2
Upper boiler temperature
10 … 90 °C
80 °C
Volt 2
Upper voltage
0.0 … 10.0 V
8.0 V
Tmin
Minimum boiler temperature
1 … 90 °C
10 °C
Tmax
Maximum boiler temperature
1 … 90 °C
80 °C
Sen. Flow
Flow sensor option
Yes, No
No
Sensor
Flow sensor selection
system dependent
S4
Interval
Monitoring period
10 … 600 s
30 s
Hysteresis
Correction hysteresis
0.5 … 20.0 K
1.0 K
Correction
Correction of the voltage signal 0.1 … 1.0 V
0.1 V
Min. runtime Minimum runtime option
Yes, No
No
Min. runtime Minimum runtime
0 … 120 min
10 min
Pump 1 … 2
Shared relay option for loading
pump
Activated, Deactivated Deactivated
Adjustment
channel
Description
Adjustment range /
selection
Factory setting
Relay
Relay selection
system dependent
system dependent
Start-up
Pump delay
No, Time, Temperature No
Delay
Delay to a demand
0 … 300 s
60 s
TStart-up
Boiler start-up temperature
10 … 90 °C
60 °C
Overrun
Pump overrun
No, Time, Temperature No
Overrun time Overrun time
0 … 300 s
60 s
TOverrun
Remaining boiler temperature
10 … 90 °C
50 °C
Sensor Boiler
1 … 2
Boiler sensor selection
system dependent
system dependent
Valve 1 … 2
Activation of a shared relay
Parallel relay
Activated, Deactivated Deactivated
Relay
Relay selection
system dependent
system dependent
back
In this menu, up to 2 heating demands can be activated and adjusted.
Activated demands will be available for selection in the output alloca-
tion channels of the backup heating in heating circuits and heating op-
tional functions. This way, several heating circuits and optional functions
can demand the same heat source.
Every demand can be carried out by means of a relay and/or a 0-10 V output.
If both the Relay and the 0-10 V option are activated, the demand will use both
outputs in parallel.
Relay option
If the Relay option is activated, the sub-menu Relay appears, in which a relay can
be allocated to the demand.
The options Boiler protection min and Boiler protection max can be acti-
vated for the demand via a relay, allowing temperature-dependent control of the
boiler demand. For this purpose, a boiler sensor (Sensor Boiler) is required.
The Boiler pr. min option is used for protecting an older type boiler against
cooling. If the temperature falls below the adjusted minimum temperature, the
allocated relay is energised until the minimum temperature is exceeded by 2 K.
The Boiler pr. max option is used for protecting an older type boiler against
overheating. If the adjusted maximum temperature is exceeded, the allocated relay
is switched off until the temperature falls by 2 K below the maximum temperature.