With the menu item Function, an optional function already selected can be tem-
porarily deactivated or re-activated respectively. All adjustments remain stored,
the allocated relays remain occupied and cannot be allocated to another function.
If the menu item Delete function is confirmed by pressing button
➄
, a security
enquiry appears. The setting can be changed between Yes and No by pressing
buttons
❷
and
❹
. If Yes has been selected and confirmed by pressing button
➄
,
the function is deleted and available under Add new function again. The corre-
sponding relays are available again.
Parallel relay
Arrangement / Opt. functions / Add new function / Parallel relay
Adjustment
channel
Description
Adjustment range /
selection
Factory setting
Relay
Relay selection
system dependent
system dependent
Ref. relay
Reference relay selection
system dependent
system dependent
Delay
Delay option
Yes, No
No
Duration
Delay time
1 … 30 min
1 min
Overrun
Overrun option
Yes, No
No
Duration
Overrun time
1 … 30 min
1 min
Inverted
Inverted switching option
Yes, No
No
Funct.
Activation / Deactivation
Activated / Deactivated Activated
Note:
If a relay is in the manual mode, the selected parallel relay will not be
energised.
The Parallel relay function can be used for operating an allocated parallel relay
alongside a selected reference relay. With this function, e. g. a valve can be con-
trolled in parallel to the pump via a separate relay.
If the Overrun option is activated, the parallel relay remains switched on for the
adjusted overrun time after the reference relay has been switched off.
If the Delay option is activated, the parallel relay will be energised after the ad-
justed delay time has elapsed. If the reference relay is switched off again during the
delay time, the parallel relay will not be switched on at all.
If the Inverted option is activated, the parallel relay switches on when the refer-
ence relay switches off and vice versa.