22
Installation
Commissioning
Settings
Data comm
unication
Tr
oubleshooting
en
1,0
Flo
w temperatur
e in °C
Outdoor temperature in °C
Flo
w set star
t value in °C at r
oom factor = 10
Heating curves
20
30
40
60
50
70
Room influence
If the heating system Constant is selected, the Room influence option will be
available. The weather-compensated set flow temperature will thus be expanded
by a demand-based room control.
The parameter Room factor can be used for determining the intensity of the
room influence.
Heating system Curve:
Set flow temperature = heating curve tempe remote c day cor-
rection or night correction.
The Remote control allows manual adjustment of the heating curve (± 15 K). Fur-
thermore, the heating circuit can be switched off or a rapid heating can be carried
out by means of the remote control.
Heating circuit switched off means that the heating circuit pump is switched off
and the mixer closed. The flow temperature is boosted to maximum for rapid
heating when the remote control is set to rapid heating.
The calculated set flow temperature is limited by the adjusted values of the pa-
rameters set flow temperature and minimum flow temperature .
Maximum flow temperature
≥
set flow temperature
≥
minimum flow temperature
The parameter Pump off is used for switching off the heating circuit pump, if the
adjusted value of the maximum flow temperature is exceeded by 5 K.
If the outdoor temperature sensor is defective, an error message will be indicated.
For the duration of this condition, the maximum flow temperature -5 K is assumed
as the set flow temperature.