Installation
31
Commissioning
Settings
Tr
oubleshooting
Data comm
unication
en
DHW heating
The DHW heating is used for demanding a backup heating for heating the DHW
store.
For the DHW heating, 2 different modes are available:
Thermal mode
The allocated demand relay is switched on when the temperature at the allocated
sensor 1 falls below the adjusted switch-on temperature. If the temperature at the al-
located sensor exceeds the adjusted switch-off temperature, the relay is switched off.
Zone mode
If the Zone mode is selected, the switch-on and switch-off conditions must be
fulfilled at 2 sensors for the relay to switch on or off respectively.
If the Load. temp. option is activated, the actuator of the transmission station
controls the outlet temperature at the secondary side to Toff +
D
TFlow.
When the Timer option is activated, a timer is indicated in which time frames for
the function can be adjusted.
Note:
For information on timer adjustment see page 10.
Heating / Opt. functions / Add new function / DHW heating
Adjustment
channel
Description
Adjustment range /
selection
Factory setting
DHW heating
DHW heating
system dependent
system dependent
Mode
Mode
Therm., Zone
Therm.
Sensor 1
Reference sensor 1
system dependent
system dependent
Sensor 2
Reference sensor 2
(if mode = Zone)
system dependent
system dependent
Ton
Switch-on temperature
0 … 79 °C
40 °C
Toff
Switch-off temperature
1 … 80 °C
45 °C
Load. temp.
Increase for Toff
Yes, No
system dependent
D
TFlow
Increase for set temperature
transmission station
10 … 20 K
20 K
Timer
Timer option
Yes, No
No
Timer DHW1
Timer
00:00 … 23:45
-
Day selection
Day selection
All days, Mon-
day … Sunday, Continue
-
DHW loading p... DHW loading pump option
Yes, No
Yes
Relay
Relay selection DHW loading
pump
system dependent
system dependent
Valve
Valve option
Yes, No
No
Relay
Relay selection
system dependent
system dependent
Demand
Demand option
Yes, No
No
Relay
Relay selection
system dependent
system dependent
Boiler loading p. Boiler loading pump option
Yes, No
No
Relay
Loading pump relay selection system dependent
system dependent
SFB Off
Solid fuel boiler off option
Yes, No
No
Funct.
Activation / Deactivation
Activated / Deactivated Activated
Delete function
back