Heating / Opt. functions / Add new function / Circulation
Adjustment
channel
Description
Adjustment range /
selection
Factory setting
Mode
Variant
Demand, Thermal, Timer,
Timer, Therm.+-
Timer
Thermal
Sensor
Circulation sensor selection system dependent
system dependent
Ton
Switch-on temperature
10 … 59 °C
40 °C
Toff
Switch-off temperature
11 … 60 °C
45 °C
Delay
Demand switch-on delay
0 … 3 s
0 s
Runtime
Runtime
01:00 … 15:00 min
03:00 min
Break time
Break time
10 … 60 min
30 min
Timer
Time frame adjustment
00:00 … 23:45
-
Day selection
Day selection
All days, Monday … Sunday,
Continue
-
Circ. pump
Circulation pump option
Yes, No
Yes
Relay
Relay selection
system dependent
system dependent
Valve
Valve option
Yes, No
No
Relay
Relay selection
system dependent
system dependent
Demand
Demand option
Yes, No
No
Relay
Relay selection
system dependent
system dependent
Boiler loading p. Boiler loading pump option Yes, No
No
Relay
Relay selection
system dependent
system dependent
SFB Off
Solid fuel boiler off option Yes, No
No
Funct.
Activation / Deactivation
Activated / Deactivated
Activated
Transmission station
The Transmission station function is used for controlling the temperature at
the flow of the secondary circuit of the transmission station to the temperature
required by the loads (e.g. heating circuit). If the function is activated, the transmis-
sion station is available as the virtual relay Tr.st. in the relay allocation channels of
the demands. Therefore, several heating circuits and optional functions (heating)
can demand the same heat source. The return maximum limitation controls
the temperature at the return sensor of the primary circuit so that it reaches the
adjusted temperature TMax in order to avoid transferring too high temperatures
to the local heating grid.
Heating / Opt. functions / Add new function / Transm. station
Adjustment
channel
Description
Adjustment
range / selection
Factory setting
Primary
Primary circuit
Sen. Flow
Flow sensor primary circuit
system dependent S8
Sen. Return Return sensor primary circuit
system dependent S7
Actuator
Actuator primary circuit
system dependent B
RE limitation
Return maximum limitation primary
circuit
Yes, No
Yes
TMax
Return maximum temperature primary
circuit
10 … 100 °C
50 °C
Secondary
Secondary circuit
Sen. Flow
Flow sensor secondary circuit
system dependent S5
Sen. Return Return sensor secondary circuit
system dependent S6
Set temp.
Set temperature option secondary
circuit
Yes, No
Nein
Tset
Set temperature secondary circuit
10 … 100 °C
40 °C
Module
Changeover module option
Yes, No
system dependent
Pump
Relay selection pump
system dependent system dependent
Valve
Relay selection valve
system dependent system dependent
S8
S7
B
S5
S6