background image

Z334-E1-01A

Cat. No.

Fixed Laser-Type
Barcode Reader

User’s Manual

V500-R2 Series

Summary of Contents for V500-R2 Series

Page 1: ...Z334 E1 01A Cat No Fixed Laser Type Barcode Reader User s Manual V500 R2 Series...

Page 2: ...performance and application methods of the V500 R2 series This manual is intended for personnel with knowledge of electrical systems Be sure to read and understand this manual thoroughly before using...

Page 3: ...Appendix Introduction Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 READ AND UNDERSTAND THIS DOCUMENT Be sure to read this Product Overview Wiring and Installation Function Explanation S...

Page 4: ...REGARDING THE PRODUCTS UNLESS OMRON S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED STORED INSTALLED AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION ABUSE MISUSE OR INAPPROPRIATE MODIFICA...

Page 5: ...improvements and other reasons It is our practice to change model numbers when published ratings or features are changed or when significant construction changes are made However some specifications o...

Page 6: ...which if not avoided will result in minor or moderate injury or may result in serious injury or death Additionally there may be significant property damage Indicates a potentially hazardous situation...

Page 7: ...ser regulations For the Safety Use of Laser Products Avoid eye exposure to direct or scattered radiation reflected by a mirror surface Laser beam emitted from a laser has high power density and may be...

Page 8: ...rotection Class 3B laser products not exceeding five times the AEL of Class 2 in the wavelength range of 400 nm to 700 nm are to be treated as Class 3A laser products Classification Class 1 Class 2 Cl...

Page 9: ...sistance be sure to use S8VS 01505 made by OMRON as a driving power supply Do not connect a voltage or AC power supply that has a voltage exceeding the rating voltage 5 V 10 Avoid reverse connection o...

Page 10: ...the product Dispose of the product as industrial waste If the product becomes extremely hot or abnormal odors or smoke are emitted stop using the product immediately turn the power OFF and consult wi...

Page 11: ...r supply connection and wiring Be sure to use S8VS 01505 made by OMRON as a driving power supply Do not install the product in a location where a high voltage device is installed Be sure to user the s...

Page 12: ...o electronic sensor mount the bar code reader so that the footlight beam of the photo electronic sensor does not spot directly on the reading window of the bar code reader or on the bar code 5 Influen...

Page 13: ...aracter or more and 2 5 mm or more is necessary of both right and left side of the label Rough standard 12 or 13 times or more of the narrow bar width 8 To improve reading reliability When the digit i...

Page 14: ...Creating Setting Files Using the 2DCR Configear Creates the data setting file for loading set data to the Handheld 2D Code Reader Make the settings for the communications conditions functions and disp...

Page 15: ...Introduction Visual Aids Indicates points that are important in using product functions or in application procedures Indicates page numbers providing related information Indicates helpful information...

Page 16: ...recautions for Correct Use 9 How to Use This Manual 12 Visual Aids 13 Contents 14 Section 1 Product Overview 17 Features 18 Product Composition 20 Part Names 21 Rating Performance 22 Usage Flow Chart...

Page 17: ...mple of System Configuration 97 Example of Connection with a PC 98 Example of Connection with Programmable Controller CS1 99 Example of Multi drop Connection 102 How to Use Command Link Unit V700 L12...

Page 18: ...16 V500 R2 series User s Manual Introduction Contents Introduction MEMO...

Page 19: ...V500 R2 series User s Manual Section 1 Product Overview This section explains about features and rating performance of this bar code reader Features 18 Product Composition 20 Part Names 21 Rating Perf...

Page 20: ...tion work and maintenance work hour can be greatly reduced p 48 Simple function setting You can either set the function by reading a menu sheet or by inputting a command on the upper equipment You can...

Page 21: ...ility and wide reading distance of 70 mm to 330 mm in case of narrow bar width 1 0 mm p 24 Easy multi drop Connect communication link unit V700 L12 to collect read data from plural bar code readers ma...

Page 22: ...n which the bar code reader reads and refers with the registered information and records V500 R2 series Tip of the cable is a connector Use an appropriate connecting cable according to the upper equip...

Page 23: ...ction 1 Part Names Section1 Product Overview Part Names Front side Back side Reading window Laser beam radiates from here Main cable Laser alarm label SCAN button Press it once to read once READ OK LE...

Page 24: ...es on curved surfaces R R 20mm UPC 12 digit Light source Red laser diode Wave length 650 nm Light output 1 0m W or less Correspond to JIS class 2 Scan type Raster scan Number of scan 1000 scan sec Int...

Page 25: ...minutes each 10 times Degree of protection IP54 IEC60529 Weight Main unit only Approximately 80 g Including accessories Approximately 190 g including mounting bracket insulation plate and screws Packa...

Page 26: ...conditions Contrast MRD 63 PCS 0 9 Bar code CODE39 Installation condition Pitch angle 0 skew angle 15 Tilt angle 0 curvature R 1 Distance from the end of the case Narrow bar width Reading distance 1...

Page 27: ...39 9 digits PCS 0 9 Reading distance 110 mm from the case end Installation condition Skew angle 15 tilt angle 0 curvature R Skew angle In the following conditions readable up to 60 However range from...

Page 28: ...to the bar code height Scan all the bar code with the laser Curvature In case of the following conditions the bar code of 8 digit EAN curvature range 15 mm or more and 13 digit EAN curvature range 20...

Page 29: ...e type width height and numbers of digit of bar codes p 22 Rating Performance p 136 Corresponding Bar Code List Wiring p 30 Wiring Connect peripheral equipment p 97 Example of System Configuration Che...

Page 30: ...age environment p 48 Test Reading Function Execute reading Read only the registered bar code p 79 Setting for label registration In case of trouble A bar code cannot be read correctly p 129 Troublesho...

Page 31: ...Wiring and Installation 29 V500 R2 series User s Manual Section 2 Wiring and Installation This section explains about the wiring method and installation method of the bar code reader Wiring 30 Instal...

Page 32: ...voltage exceeding the rating voltage 5 V 10 Avoid reverse connection of power supply Do not short circuit a load on OK NG output signal open collector Wire color Pin No Signal name Function Signal dir...

Page 33: ...orporation TCS8587 0170477 For panel installation 2 Hosiden Corporation TCS1080 0120177 Logic of external trigger signal can be selected You can select the output logic of READ OK and READ NG signal M...

Page 34: ...NG signal output circuit Cable specification Shape Straight cable Diameter 3 8 mm Length 1500 50 mm Number of core 9 Item Specification Output system NPN open collector Rated load 24 VDC 30 mA Leak c...

Page 35: ...ng bracket to the barcode reader M3 screws Tightening torque 0 54 N m 2 Install M5 screws Tightening torque 2 3 N m Do not apply stress on the cable when installing or using Distance and angle allowed...

Page 36: ...34 Section 2 Installation V500 R2 series User s Manual Section 2 Wiring and Installation MEMO...

Page 37: ...2 series User s Manual Section 3 Function Explanation This section explains about representative functions of the bar code reader Explanation of Reading System 36 Operation Flow Chart 37 Communication...

Page 38: ...the trigger is ON Ignored even when input RS 232C command The upper equipment sends the communication command and the laser beam radiates to start reading After receiving the command it reads only for...

Page 39: ...e this clause 2 In case of trigger controlled system reads while the trigger is ON consider that the reading effective duration is set to 0 Power on Wait for the reading trigger Laser radiation Readin...

Page 40: ...the reading effective duration is set to 0 Power on Wait for the eading trigger Laser radiation Reading process execution Is reading succeeded Repeat Is reading trigger end 1 Has reading effective du...

Page 41: ...ger is ON consider that the reading effective duration is set to 0 Power on Wait for the reading trigger Laser radiation Reading process execution Is reading succeeded Repeat Is reading trigger end 1...

Page 42: ...waits for the upper equipment response after transmitting the data When ACK 06H 1 byte is received from the upper equipment buzzer sounds indicating the normal finishing and ends data transmission Wh...

Page 43: ...ng to communication condition In case of continuous reading and plural reading laser is always radiating during trigger input is ON or during reading effective duration Concept of T0 to T4 other than...

Page 44: ...imum OFF time Be sure to set 30 ms or more T4 Communication time Differs according to communication condition In case of continuous reading and plural reading laser is always radiating during trigger...

Page 45: ...condition Operation Flow Chart p 37 Confirmation of trigger input timing When constructing the system to read the moving bar code input timing of the external trigger signal is important Input the ext...

Page 46: ...tion against the scanning direction As the appropriate direction differs according to the size of a label investigate when installing Bar code moving direction Scanning range Whole height of a bar cod...

Page 47: ...Reading trigger input by RS 232C command Reading trigger command format is as shown below Set command input Reading condition set command can be transmitted from the upper equipment Format is as foll...

Page 48: ...Setting method p 73 Output item Description Initial setting Header Letter strings to add at the head of transmitted data Max 4 arbitrary characters can be set No header Number of digit Number of digi...

Page 49: ...ust the number of digit to be in accordance with EAN 13 0 S X1 X2 X3 X4 X5 X6 C D S Number system character Automatically decided according to the combination of each character of X1 to X10 EAN Readin...

Page 50: ...To finish the reading rate measurement mode enter command W or re start the bar code reader Return to the normal measurement mode Output format Reading rate of every one sec is output to the upper equ...

Page 51: ...is at still state when read reading is possible without problem However when the target bar code is moving reading may be failed according to speed 26 50 There is a possibility to fail even reading a...

Page 52: ...50 Section 3 Test Reading Function V500 R2 series User s Manual Section 3 Function Explanation MEMO...

Page 53: ...51 V500 R2 series User s Manual Section 4 Setting Method This section explains about setting methods using a menu sheet and entering command from the upper equipment How to Use Menu Sheet Command 52 M...

Page 54: ...code reader entered setting mode _ZZ_ 2 Read U2 on the menu sheet that means to return to factory default setting _U2_ 3 Read the item on the menu sheet you want to change setting Menu Sheet Command L...

Page 55: ...system of CODE39 However the code is special using start code and stop code for a space mark Normally You can create a menu sheet using bar code creation software available in the market as shown bel...

Page 56: ...he bar code reader is processing command it notifies externally that it is in processing mode turning off the RS signal line When the RS signal line is not connected interval between inputting command...

Page 57: ...g codes directly E g 2 Set AB CR on header When designating hexadecimal number directly 00H zero cannot be designated as header or footer It is regarded as end character Characters until just before 0...

Page 58: ...ion and prohibition p 62 Detail setting for reading code p 64 Setting for the number of times of reading coincidence p 69 Setting for reading operation p 70 Setting for reading effective duration p 70...

Page 59: ...putting a command from the upper equipment When you turn the power OFF without writing the setting in the memory the settings will be lost Setting for external trigger signal Select positive logic or...

Page 60: ...l settings Not calculate C D Transfer C D Not transfer ST SP Codabar NW 7 detail settings Not calculate C D Transfer C D Not transfer ST SP Data character of at least 5 digits Industrial2of5 STF detai...

Page 61: ...signals Signal output system External trigger synchronous system positive logic H active Label registration None Communication conditions Communication speed 9600 bps Data length 8 bits Parity None S...

Page 62: ...dabar NW 7 Transfer ST SP of Codabar NW 7 abcd abcd ITF Industrial2of5 STF detail setting Invalid C D of ITF Industrial2of5 STF Transfer C D of ITF Industrial2of5 STF Reading condition Reading system...

Page 63: ...Invalid C D of ITF Industrial2of5 STF Transfer C D of ITF Industrial2of5 STF Reading condition Reading system Trigger reading Reading operation Single reading Reading valid time Trigger 2 sec Number o...

Page 64: ...All codes except add ons Factory default setting _A0_ A0 Reading prohibition for all codes _B0_ B0 Reading permission for UPC codes _R1_ R1 Permission for UPC add on 2 digit codes _R2_ R2 Permission f...

Page 65: ..._R7_ R7 Reading permission for ITF codes _R8_ R8 Reading permission for CODE128 codes _B6_ B6 Reading permission for CODE93 codes _B5_ B5 Reading permission for GS1 DataBar RSS 14 codes _JX_ JX Readi...

Page 66: ...sheet Command Transfer C D without an 0 in the beginning Factory default setting _E3_ E3 Not transfer C D without an 0 in the beginning _E5_ E5 Transfer C D with 0 in the beginning _E2_ E2 Not transfe...

Page 67: ...r C D Factory default setting _6K_ 6K Not transfer C D _6J_ 6J Menu sheet Command Transfer C D Factory default setting _6I_ 6I Not transfer C D _6H_ 6H Menu sheet Command Not calculate C D Factory def...

Page 68: ...tting _D1_ D1 Menu sheet Command Not calculate C D Factory default setting _H7_ H7 Calculate C D _H6_ H6 Transfer C D Factory default setting _H8_ H8 Not transfer C D _H9_ H9 Not transfer ST SP Factor...

Page 69: ...least 1 digit _HC_ HC Data character of at least 3 digits _HB_ HB Data character of at least 5 digits _HF_ HF Menu sheet Command Not calculate C D Factory default setting _G0_ G0 Calculate C D _G1_ G1...

Page 70: ...ethod GS1 128 EAN 128 GS1 Databar RSS Menu sheet Data character of at least 5 digits _GI_ GI Menu sheet Command Disable GS1 conversion Factory default setting _X 0_ X 0 Enable GS1 conversion _X 4_ X 4...

Page 71: ...erface The verification system is AND verification Continuous coincidence system This cannot be changed Menu sheet Command Reading once and verification zero times _X0_ X0 Reading twice and verificati...

Page 72: ...a trigger is input is set When it is set to 0 sec reading is controlled by the external trigger and the trigger is effective while the external trigger is ON Menu sheet Command Single reading Factory...

Page 73: ...Sheet Command List Section4 Setting Method 2 seconds Factory default setting _Y2_ Y2 3 seconds _Y3_ Y3 4 seconds _Y4_ Y4 5 seconds _Y5_ Y5 6 seconds _Y6_ Y6 7 seconds _Y7_ Y7 8 seconds _Y8_ Y8 9 secon...

Page 74: ...ode before reading the same code again Frames A frame is another representation of time ms Intervals between frames are not constant and they differ depending on codes When the frame is set to infinit...

Page 75: ...read E g In the following two examples the NL CR message is set for No label and the ND CR message for Decoding failure Those two examples may occur at the same time The error message is disabled when...

Page 76: ...e number of reading digits Error message Decoding failure _TI_ TI Not transmit an error message Factory default setting _TG_ TG To read codes of a known length it is recommended that the number of dig...

Page 77: ...nabled or disabled or its type and sound duration and volume are set The buzzer sounds when reading succeeds Menu sheet Command Disable the READ OK LED _T4_ T4 READ OK LED illumination time 200 ms Fac...

Page 78: ...zer sound duration 50 ms Factory default setting _W7_ W7 Buzzer sound duration 100 ms _W4_ W4 Buzzer sound duration 200 ms _W5_ W5 Buzzer sound duration 400 ms _W6_ W6 Buzzer sound volume Max Factory...

Page 79: ...egistered in Setting for label registration p 79 is read Menu sheet Command Output the signal Factory default setting _X Q_ X Q Not output the signal _X R_ X R External trigger signal synchronous syst...

Page 80: ...4 Setting Method One shot duration 40 ms _X J_ X J One shot duration 50 ms _X K_ X K One shot duration 60 ms _X L_ X L One shot duration 70 ms _X M_ X M One shot duration 80 ms _X N_ X N One shot dura...

Page 81: ...t does not match any of those codes Up to 5 codes can be registered E g The following describes the steps for registering labels To cancel a label registration end the setting without reading a label...

Page 82: ...nsmitted and the reader is restarted Menu sheet Command Communication speed 300 bps _K1_ K1 Communication speed 600 bps _K2_ K2 Communication speed 1200 bps _K3_ K3 Communication speed 2400 bps _K4_ K...

Page 83: ...tting Method Data length 7 bits _L0_ L0 Data length 8 bits Factory default setting _L1_ L1 Parity None Factory default setting _L2_ L2 Parity Even number _L3_ L3 Parity Odd number _L4_ L4 Stop bit 1 b...

Page 84: ...and Communication protocol No protocol system Factory default setting _P0_ P0 Communication protocol With RS CS control Ready Busy system _P1_ P1 Communication protocol ACK NAK system _P3_ P3 CS waiti...

Page 85: ...p 84 can be included as 1 digit in the header E g The following describes the steps for setting the header AB Menu sheet Command Set the headers collectively Applied to all codes _RY_ RY Clear the hea...

Page 86: ...he steps for setting the number of digit output Menu sheet Command Number of digit output Bar code 2 digits _ 3_ 3 Number of digit output Bar code 6 digits _ 6_ 6 The output format is as shown below W...

Page 87: ...Command List Section4 Setting Method Direct code designation Used to set character strings and values directly when designating the header or footer Menu sheet Command SPACE _5A_ 5A _5B_ 5B _5C_ 5C _5...

Page 88: ...86 Section 4 Menu Sheet Command List V500 R2 series User s Manual Section 4 Setting Method _5K_ 5K _5L_ 5L _5M_ 5M _5N_ 5N _5O_ 5O _5P_ 5P _6A_ 6A _6B_ 6B _6C_ 6C _6D_ 6D _6E_ 6E Menu sheet Command...

Page 89: ...87 V500 R2 series User s Manual Section 4 Menu Sheet Command List Section4 Setting Method _6F_ 6F _6G_ 6G _7A_ 7A _7B_ 7B _7C_ 7C _7D_ 7D _ _7E_ 7E _7F_ 7F _9T_ 9T _9U_ 9U _9V_ 9V Menu sheet Command...

Page 90: ...n 4 Menu Sheet Command List V500 R2 series User s Manual Section 4 Setting Method _9W_ 9W 0 _Q0_ Q0 1 _Q1_ Q1 2 _Q2_ Q2 3 _Q3_ Q3 4 _Q4_ Q4 5 _Q5_ Q5 6 _Q6_ Q6 7 _Q7_ Q7 8 _Q8_ Q8 9 _Q9_ Q9 Menu sheet...

Page 91: ...2 series User s Manual Section 4 Menu Sheet Command List Section4 Setting Method A _0A_ 0A B _0B_ 0B C _0C_ 0C D _0D_ 0D E _0E_ 0E F _0F_ 0F G _0G_ 0G H _0H_ 0H I _0I_ 0I J _0J_ 0J K _0K_ 0K Menu shee...

Page 92: ...4 Menu Sheet Command List V500 R2 series User s Manual Section 4 Setting Method L _0L_ 0L M _0M_ 0M N _0N_ 0N O _0O_ 0O P _0P_ 0P Q _0Q_ 0Q R _0R_ 0R S _0S_ 0S T _0T_ 0T U _0U_ 0U V _0V_ 0V Menu shee...

Page 93: ...0 R2 series User s Manual Section 4 Menu Sheet Command List Section4 Setting Method W _0W_ 0W X _0X_ 0X Y _0Y_ 0Y Z _0Z_ 0Z a _ A_ A b _ B_ B c _ C_ C d _ D_ D e _ E_ E f _ F_ F g _ G_ G Menu sheet Co...

Page 94: ...ection 4 Menu Sheet Command List V500 R2 series User s Manual Section 4 Setting Method h _ H_ H i _ I_ I j _ J_ J k _ K_ K l _ L_ L m _ M_ M n _ N_ N o _ O_ O p _ P_ P q _ Q_ Q r _ R_ R Menu sheet Com...

Page 95: ...2 series User s Manual Section 4 Menu Sheet Command List Section4 Setting Method s _ S_ S t _ T_ T u _ U_ U v _ V_ V w _ W_ W x _ X_ X y _ Y_ Y z _ Z_ Z NULL _9G_ 9G SOH _1A_ 1A STX _1B_ 1B Menu sheet...

Page 96: ...Sheet Command List V500 R2 series User s Manual Section 4 Setting Method ETX _1C_ 1C EOT _1D_ 1D ENQ _1E_ 1E ACK _1F_ 1F BEL _1G_ 1G BS _1H_ 1H HT _1I_ 1I LF _1J_ 1J VT _1K_ 1K FF _1L_ 1L CR _1M_ 1M M...

Page 97: ...ser s Manual Section 4 Menu Sheet Command List Section4 Setting Method SO _1N_ 1N SI _1O_ 1O DLE _1P_ 1P DC1 _1Q_ 1Q DC2 _1R_ 1R DC3 _1S_ 1S DC4 _1T_ 1T NAK _1U_ 1U SYN _1V_ 1V ETB _1W_ 1W CAN _1X_ 1X...

Page 98: ...6 Section 4 Menu Sheet Command List V500 R2 series User s Manual Section 4 Setting Method EM _1Y_ 1Y SUB _1Z_ 1Z ESC _9A_ 9A FS _9B_ 9B GS _9C_ 9C RS _9D_ 9D US _9E_ 9E DELL _9F_ 9F Menu sheet Command...

Page 99: ...tion 5 Example of System Configuration This section explains about connection method with upper equipment Example of Connection with a PC 98 Example of Connection with Programmable Controller CS1 99 E...

Page 100: ...nection with PC AT compatible PC is explained Example of BASIC program 100 CLS 110 CLOSE 1 120 OPEN COM N81NN AS 1 130 BCDATA 140 AA INPUT 1 1 150 IF AA CHR H03 GOTO 170 160 BCDATA BCDATA AA GOTO 140...

Page 101: ...tion with programmable controller CS1 Made by OMRON is explained Connect the connection cable of this bar code reader to RS 232C port of the CPU unit Special cable V509 W011 Bar code reader V500 R2 se...

Page 102: ...ration manual of your programmable controller Setting item Setting content Command Communication speed 9600 bps Same as initial setting Data length 7 bit L0 Parity Even number L3 Stop bit 2 bit L6 Hea...

Page 103: ...ed To check the read data with the programming console press Clear FUN Monitor in this order For the program command refer to the operation manual of your programming console Items related to communic...

Page 104: ...ng to the interface RS 485 or RS 232C of the upper equipment side Example of connecting communication link unit hereinafter referred to as link unit and the upper equipment using RS 485 is described i...

Page 105: ...bps Same as initial setting Data length 8 bit Same as initial setting Parity Even number L3 Stop bit 1 bit Same as initial setting Header None Same as initial setting Footer CR Same as initial setting...

Page 106: ...d from the upper equipment the link unit transmits the stored read data to the upper equipment Communication converter PC AT compatible PC Execution of reading Link unit Machine No 01 Machine No 02 Ma...

Page 107: ...equipment E g When exporting data of machine No 2 Reading data transmitted from the bar code reader E g When the reading data of the machine No 2 is ABCDE E g When the read data is not accumulated Whe...

Page 108: ...bar code reader and the link unit is described here When used be sure to read the operation manual of the link unit V700 L12 LED Description RUN Illuminate during normal operation of the link unit COM...

Page 109: ...At operation 0 to 45 C At storage 15 to 50 C without freeze or dew condensation Ambient humidity At operation and storage 35 to 85 RH without due condensation Enclosure rating IP20 IEC60529 Standard...

Page 110: ...is a power terminal The terminal mounting screw size is M3 Use a crimping terminal which fits to M3 screw Connect 24 V power supply device Recommended device Shape Size Fork type Round type Manufactu...

Page 111: ...29 OFF OFF ON ON ON 14 ON OFF ON ON OFF 30 ON OFF ON ON ON 15 OFF ON ON ON OFF 31 OFF ON ON ON ON 16 ON ON ON ON OFF Setting not allowed ON ON ON ON ON Setting item Initial setting Description Communi...

Page 112: ...ormat fixed Start bit Data bit Parity bit Stop bit Total 1 8 None 1 10 Check code Error detection system FCS Frame Check Sequence Vertical parity system Pin No Signal name Function Signal direction 1...

Page 113: ...or link unit side 2 When CS function is used on PC side a return line is required Model Manufacturer Cable CO MA VV SB 5PX28AWG Hitachi Cable Ltd Connector Socket XM2D 0901 OMRON Corporation Hood XM2...

Page 114: ...munication system In compliance with RS 485 Synchronous system Asynchronous system Communication control system One to N procedure dedicated to OMRON Communication speed 4800 9600 19200 38400 bps Set...

Page 115: ...line MVVS 2CX0 5SQ Tachii Electric Wire Co Ltd Frame ground wire Cables of AWG22 to 20 Crimping terminal When connecting one wire to one terminal AI0 5 8WH PHOENIX CONTACT When connecting two wires t...

Page 116: ...chronous system Asynchronous system Communication control system One to one procedure dedicated to OMRON Communication speed fixed 9600 bps Character format fixed Start bit Data bit Parity bit Stop bi...

Page 117: ...to transmit to the bar code reader However in case when the first character is DLE 10 h it is handled as link unit process command defined by the next character P 50 h Polling Invalid in case of throu...

Page 118: ...there is no data in buffer In case of Through procedure normal output procedure no response is output even if command is input Resend request R The response sent before is transmitted again Input comm...

Page 119: ...on frame with the bar code reader to STX to ETX Y Input command Response When a code other than 00 is returned p 120 Communication frame with the bar code is as shown below However it returns to defau...

Page 120: ...erformed for normal operation Upper equipment RS 232C 24 V power source 24 V power source 24 V power source 24 V power source Bar code reader Bar code reader Bar code reader Bar code reader DIP SW 1 t...

Page 121: ...e performed for normal operation Upper equipment 24 V power source 24 V power source 24 V power source 24 V power source Bar code reader Bar code reader Bar code reader Bar code reader DIP SW 1 to 5 S...

Page 122: ...he command and the machine No setting on the link unit side Command format CR calculation of check codes distance of command characters etc RS 232C cable wiring effect of circumference noise There are...

Page 123: ...es are returned as a response error occurred Check by referring following table End code Error cause Check point 93 Bar code reader communication malfunction Cable wiring of the bar code reader effect...

Page 124: ...122 Section 5 How to Use Command Link Unit V700 L12 V500 R2 series User s Manual Section 5 Example of System Configuration MEMO...

Page 125: ...Section 6 Appendix 123 V500 R2 series User s Manual Section 6 Appendix External Dimension 124 Troubleshooting 129 ASCII Code Table 130 Explanation of Terms 131 Corresponding Bar Code List 136...

Page 126: ...ode reader V500 R2CF 13 5 6 6 29 5 4 3 6 25 3 7 17 7 3 7 0 2 16 37 18 54 3 2 13 38 5 6 2 1 3 8 1 5 5 5 6 6 5 0 1 5 1 4 2 9 2 0 1 2 4 45 8 1 R 7 19 2 M5 Unit mm M3 Depth 3 M3 Depth 3 Light axis Connect...

Page 127: ...round cord 5 1 Pink external trigger Brown 5V Blue 0V Vinyl insulated round cord 3 8 3 core conductor section area 0 2 mm2 diameter of insulation body 1 0 mm Signal name No FG 1 SD 2 RD 3 RS 4 CS 5 6...

Page 128: ...al trigger Brown 5V Blue 0V Vinyl insulated round cord 4 7 3 core conductor section area 0 2 mm2 diameter of insulation body 1 0 mm Signal name No 1 RD 2 SD 3 ER 4 SG 5 DR 6 RS 7 CS 8 9 Shield wire Co...

Page 129: ...external trigger Blue 0V Vinyl insulated round cord 3 8 2 core conductor section area 0 2 mm2 diameter of insulation body 1 0 mm Signal name No 1 SD 2 RD 3 RS 4 CS 5 5V 6 0V 7 8 SG 9 Shield wire Conn...

Page 130: ...128 Section 6 External Dimension V500 R2 series User s Manual Section 6 Appendix Communication link unit V700 L12 Unit mm Dimension of mounting hole process 2 M4 or 4 2 2 4 5...

Page 131: ...tion setting content Especially check the operation mode and data output mode 2 Is the bar code mounted or does it pass at the reader reading position 3 Are there enough margin on both sides of the ba...

Page 132: ...4 ENQ 05 25 E 45 e 65 ACK 06 26 F 46 f 66 BEL 07 27 G 47 g 67 BS 08 28 H 48 h 68 HT 09 29 I 49 i 69 LF 0A 2A J 4A j 6A VT 0B 2B K 4B k 6B FF 0C 2C L 4C l 6C CR 0D 2D M 4D m 6D S0 0E 2E N 4E n 6E S1 0F...

Page 133: ...Number of conformance should be at least twice number of verification is once to increase reliability Narrow bar slim bar The narrower bar in the bar code consists with horizontal bars is called a na...

Page 134: ...Add the digits in the even positions the rightmost character is the 1st digit and multiple it by 3 2 Add up the odd numbers excluding the rightmost check digit in the data digit 3 Add values of above...

Page 135: ...Table 1 Table 1 Character value calculated in Modulus 43 E g When message CODE39 is indicated in CODE39 Therefore data with check character is CODE39R Character Value Character Value Character Value...

Page 136: ...In other cases take the reminder value from 16 and the result is the check character value 4 Result of clause 3 is the check character value shown in table 2 Table 2 Character value calculated in Modu...

Page 137: ...flection ratio is 85 or more RS CS control Control system to communicate data between the bar code reader and the upper equipment Data is transmitted while verifying to hardware through RS CS line whe...

Page 138: ...136 Section 6 Corresponding Bar Code List V500 R2 series User s Manual Section 6 Appendix Corresponding Bar Code List Bar code EAN UPC CODE39 Industrial2of5 STF Codabar NW 7 CODE93 ITF CODE128...

Page 139: ...R2 series User s Manual Section 6 Corresponding Bar Code List Section 6 Appendix GS1 DataBar RSS GS1 DataBar Omni directional GS1 DataBar Truncated GS1 DataBar Stacked GS1 DataBar Limited GS1 DataBar...

Page 140: ...36 End setting 57 External dimension figure 124 External trigger signal 31 36 57 F Factory default setting 58 Failed reading 73 Flow chart 37 Footer 83 Frame 72 Full time reading 36 G GS1 DataBar RSS...

Page 141: ...output 30 READ OK signal 77 Reading angle 25 Reading coincidence 69 Reading failed 46 Reading operation 36 70 Reading permission prohibition 62 Reading range 24 Reading rate measurement mode 48 Readi...

Page 142: ...ry A manual revision code appears as a suffix to the catalog number at the bottom of the front and back covers Reprint code Date Revised contents 01 January 2013 Original production 01A March 2013 Min...

Page 143: ......

Page 144: ...l 1 847 843 7900 Fax 1 847 843 7787 Contact www ia omron com Tokyo JAPAN OMRON ASIA PACIFIC PTE LTD No 438A Alexandra Road 05 05 08 Lobby 2 Alexandra Technopark Singapore 119967 Tel 65 6835 3011 Fax 6...

Reviews: