24
Operation Keys
Name
Function
Level Key
The parameter items are divided into three display groups (Refer
to display levels 0 to 2 in the table below). Press this key to
switch from one group to another. The display levels
automatically cycle in the sequence 0 –> 1 –> 2 –> 0 when the
key is held down for approximately 2 seconds.
Display Key
Press this key to select the required parameter from the selected
display level 0 to 2 (Refer to table below).
The parameters cycle automatically when the key is held down.
Loop Key
Press this key for approximately two seconds to switch between
Loop 1 and Loop 2.
Up Key
Press this key to increment SV.
The SV increment continuously while the key is held down. The
SV display blinks when the value reaches its upper limit.
Down Key
Press this key to decrement an SV.
The SV decreases continuously while the key is held down. The
SV display blinks when the value reaches its lower limit.
3-4
Parameter Displays and Settings
3-4-1 Table of Parameters
Display
level
Parameter
Display
symbol
Write
Read
Loop
no.
Bank
no.
Data range
Default value
Page
0
PV monitor
(see note 3)
---
No
Yes
Yes
No
Scaling lower
limit –10% to
scaling upper
limit +10%
(Unit: EU)
Manual output
volume
(see note 6)
o
Yes
Yes
Yes
No
-5 to 105%
0%
Set point (see
note 3)
---
Yes
Yes
Yes
Yes
Scaling lower
limit to scaling
upper limit
0 EU
Bank number
bk
See
note 5
Yes
Yes
No
1 to 8
1
Alarm SV 1 (see
notes 3, 4)
al–1
Yes
Yes
Yes
Yes
Alarm mode
1, 4, 5:
0 to 9999
0 EU
Alarm SV 2 (see
notes 3, 4)
al–2
Yes
Yes
Yes
Yes
0 to 9999
Other:
–999 to 9999
Input shift value
(see note 3)
in–5
Yes
Yes
Yes
Yes
–999 to 9999
0 EU
Proportional band
(see note 1)
p
Yes
Yes
Yes
Yes
0.0 to 999.9% FS
10.0% FS
Integral (reset)
time (see note 1)
i
Yes
Yes
Yes
Yes
0 to 9999 s
240 s
Derivative (rate)
time (see note 1)
d
Yes
Yes
Yes
Yes
0 to 9999 s
40 s
Parameter Displays and Settings