10
Normal
Parameters can be designated as required using
commands (Refer to
Fixed
Parameters are allocated in advance.
4-1 Memory Allocation for details of the memory contents.
Setting Direction
Selects whether the data settings are made from the Data Setting Console or
from the C200H PC, using a user program or Programming Console.
Executed Bank Number
The setting of the executed bank number is made from the C200H PC, regard-
less of the ON/OFF setting of this switch.
Input Type
SW202
Input type setting
8
9
0
1
2
4
3
5
6
7
Switch number
Loop 1
Loop 2
0
4 to 20 mA
4 to 20 mA
1
1 to 5 V
1 to 5 V
2
0 to 5 V
0 to 5 V
3
0 to 10 V
0 to 10 V
4
4 to 20 mA
1 to 5 V
5
4 to 20 mA
0 to 5 V
6
4 to 20 mA
0 to 10 V
7
1 to 5 V
0 to 5 V
8
1 to 5 V
0 to 10 V
9
0 to 5 V
0 to 10 V
The switch is factory-set to 0.
The selected position is shown by the arrow. Turn the switch with a small flat-
blade screwdriver.
The permissible setting range for measurement is –999 to 9999 (EU).
Operation and Function Setting
SW203
Operation and Function Setting
13
4
5
6
2
OFF
ON
NO
Switch Settings