alarm with standby sequence” is selected, the standby sequence recognizes
that the value is out of the alarm range and then outputs an alarm when the value
enters the alarm range once more.
Lower Limit Alarm with Standby Sequence
Hysteresis
OFF point
Standby sequence
cancel point
Alarm SV
Alarm output
0
°
C
The standby sequence is restarted in the following situations.
•
When the power is turned on.
•
When the set point is changed.
•
When the executed bank number is changed.
•
When the ALARM mode is changed.
•
When changing from stop to run.