55
Appendix A
Specifications
General Specifications
Conforms to the C200H PC specifications.
Item
C200H-PID0
j
Specifications
Input signal refresh
4 to 20 mA, 1 to 5 V, 0 to 5 V, 0 to 10 V
No. of input points (loops)
Two points (two loops, each of which consists of a voltage and a current)
Control mode
PID, ON/OFF (selectable with a switch on the rear panel)
(advanced PID control with auto-tuning)
Setting/designation accuracy
±
0.5% FS
±
1 digit max. The SV and displayed value match. There is no relative error.
Hysteresis
0.0 to 100.0% FS (in units of 0.1 %FS)
Alarm hysteresis
0.0 to 100.0% FS (in units of 0.1 %FS)
Proportional band
0.0 to 999.9 (in units of 0.1)
Integral (reset) time
0 to 9999 s (in units of 1 s)
Derivative (rate) time
0 to 9999 s (in units of 1 s)
Control period
1 to 99 s (in units of 1 s)
Sampling period
100 ms
Output refresh period
100 ms
Display refresh period
100 ms
Input shift range
–999 to 9999 (see note 1)
Scaling setting range
–999 to 9999 (see note1)
Digital filter setting range
0 to 100 s (in units of 1 s)
Alarm output setting range
–999 to 9,999
Manual output setting range
–5 to 105%
No. of banks
8 banks
Internal current consumption
5 VDC, 0.33 A max.
External supply voltage
24 VDC
+10%
/
–15%
, 0.2 A min.
Dimensions (see note 2)
34.5 mm (W) x 130 mm (H) x 120.5 mm (D)
Weight
360 g
Note 1. The decimal point position is designated by a parameter setting.
2. Refer to
Appendix B Dimensions.