40
4-1-3 Table of Commands
The command codes shown below are set in bits (Wd n) 07 to 00 when the
SW2-1 (switching memory contents) on the front panel is set in the Normal posi-
tion.
EEPROM Write/Read Commands
Parameter
Com-
mand
Write
Read
Loop
no.
Bank
no.
Actual data
range
SV data
range
Default value
Set point (see note 3)
0
0
Yes
Yes
Yes
Yes
Scaling lower limit to scaling
upper limit
0 EU
Manual output volume
(see note 6)
0
1
Yes
Yes
Yes
No
-5 to 105%
F005 to
0105
0%
Execution bank number
0
2
Yes
Yes
Yes
No
1 to 8
0001 to
0008
1
Alarm SV 1 (see notes
3, 4)
0
3
Yes
Yes
Yes
Yes
Alarm mode
1, 4, 5:
0 to 9999
0000 to
9999
0 EU
Alarm SV 2 (see notes
3, 4)
0
4
Yes
Yes
Yes
Yes
0 to 9999
Other:
–999 to 9999
9999
F999 to
9999
0 EU
Input shift value (see
note 3)
0
5
Yes
Yes
Yes
Yes
–999 to 9999
F999 to
9999
0 EU
Proportional band (see
note 1)
0
6
Yes
Yes
Yes
Yes
0.0 to 999.9
0000 to
9999
10.0 %FS
Integral (reset) time
(see note 1)
0
7
Yes
Yes
Yes
Yes
0 to 9999 s
240 s
Derivative (rate) time
(see note 1)
0
8
Yes
Yes
Yes
Yes
0 to 9999 s
40 s
Decimal point position
1
2
Yes
Yes
Yes
No
0 to 3
0000 to
0003
1
Scaling lower limit
1
3
Yes
Yes
Yes
No
-999 to (scaling upper limit
value – 1 digit)
0
Scaling upper limit
1
4
Yes
Yes
Yes
No
(Scaling lower limit + 1 digit)
to 9999
100.0
Control period (see note
1)
1
7
Yes
Yes
Yes
No
1 to 99 s
0001 to
0099
20 s
Hysteresis (see note 2)
1
8
Yes
Yes
Yes
Yes
0.0 to 100.0
0000 to
1000
0.2 %FS
Alarm hysteresis (see
note 4)
1
9
Yes
Yes
Yes
No
0.0 to 100.0
0000 to
1000
0.1 %FS
Digital filter
1
E
Yes
Yes
Yes
No
0 to 100
0000 to
0100
0 s
Control output variable
monitor
2
0
No
Yes
Yes
No
–5.0 to
105.0%
F050 to
1050
0.0%
Auto-tuning start/stop
(see note 1)
2
1
Yes
No
Yes
No
---
AT start =
0001
AT stop =
0000
---
Copy bank
2
2
Yes
No
Yes
No
---
---
Input-type monitor
2
3
No
Yes
No
No
0 to 9
0000 to
0009
Setting for
SW202
Alarm 1 mode
2
4
Yes
Yes
Yes
No
0 to 9
0000 to
0009
2
Alarm 2 mode
2
5
0009
Yes:
Possible.
No:
Not possible or not required.
Note
1. Only when advanced PID control is selected. (Switch 203-1 = OFF)
2. Only when ON/OFF control is selected. (Switch 203-1 = ON)
Memory Allocation