39
I/O
Data contents
Data item
Address
Bit
Word
Input
n+7
15 to 12
Loop 1
executed
bank
number
Outputs the bank number currently executed for Loop 1 and Loop
2 as 1-digit BCD data.
11 to 08
Loop 2
executed
bank
number
07 to 02
---
Not used. Each bit is set to 0.
01
SW2-2
Outputs the ON/OFF status of SW2-2 (setting direction).
0: Data Setting Console
1: C200H PC
00
SW2-1
Outputs the ON/OFF status of SW2-1 (switching memory
contents).
0: Fixed
1: Normal
n+8 Loop 1
9 L
2
15
---
Not used. Set to 0.
Loop 1/2
d
n+9 Loop 2
14
Sensor
error
Bit set to 1 if an input is not connected, an input wire
is broken, or the input data exceeds the operational
range.
status data
13 to 10
---
Not used. Each bit is set to 0.
09
MAN
ON (set to 1) for Manual Output Mode.
08
RUN
ON (set to 1) during operation.
07 to 05
---
Not used. Each bit is set to 0.
04
Control
output
Bit set to 1 when the control output (transistor or
voltage output) is ON.
03
AT
Bit set to 1 during auto-tuning (AT).
02
---
Not used. Set to 0.
01
AL1
Bit set to 1 when the value enters the set alarm
(R f
00
AL2
Memory Allocation