9
Unit no.
setting
Allocated address
0
Wd 100 to 109
1
Wd 110 to 119
2
Wd 120 to 129
3
Wd 130 to 139
4
Wd 140 to 149
5
Wd 150 to 159
6
Wd 160 to 169
7
Wd 170 to 179
8
Wd 180 to 189
9
Wd 190 to 199
The switch is factory-set to 0.
Note If the Unit number is set to an existing Unit number, an alarm occurs and the
C200H does not operate.
Turn the C200H power off before setting the Unit number. If the setting is
changed with the power on, the new setting is not valid until the power is turned
off and back on again.
Switching Memory Contents and Setting Direction
SW2
Switching memory contents and setting direction
Remove the cover and set the switch with the tip of a ballpoint pen or similar ob-
ject.
ON
1
2
OFF
O
F
F
Switch no.
Pin 1
Pin 2
Function
Switching memory contents
Setting direction
ON
Normal
C200H PC
OFF
Fixed
Data Setting Console
The new setting is valid immediately after the switch setting is changed.
Removing and Attaching the Cover
Removing the Cover
Attaching the Cover
Insert a small flat-blade screw-
driver between the case and
the cover at the top of the Unit
and lever off the cover.
Place the right edge of the
cover against the case and
press into position.
Switching Memory Contents
The contents of the allocated memory differ according to the Unit number set-
ting.
Switch Settings