66
word multiplier, do not overlap with the highest I/O words on the last Expan-
sion I/O Rack.
Continue registering word multipliers
by entering them with the WRITE key.
Automatically checks
I/O table.
This operation takes about 2 s.
Indicates word multiplier not yet specified.
Once the word has been specified
and entered with the WRITE key,
proceed to the next master.
When a word has already been registered, it
will be displayed. Press the WRITE key to
continue without changing it, or input a new
multiplier before the WRITE key to change it.
Appears when all word multipliers have
been registered, completing the operation.
Requesting input of word multiplier.
Word multiplier not yet specified.
Master number (0 to 7).
Indicates a Master.
I/O slot number.
Rack number.
00000I/OTBL WRIT
I/O CHECK G
00000I/OTBL WRIT
1-7U=RMT0*~?
00000I/OTBL WRIT
1-7U=RMT0*~0
00000I/OTBL WRIT
2-3U=RMT1*~?
00000I/OTBL WRIT
2-4U=RMT22~?
00000I/OTBL WRIT
OK
00000I/OTBL WRIT
1Ć7U=RMT0*~?
4-5-4
Clearing Error Messages
After the I/O table has been registered, any error messages recorded in
memory should be cleared. It is assumed here that the causes of any of the
errors for which error messages appear have already been taken care of. If
the beeper sounds when an attempt is made to clear an error message,
eliminate the cause of the error, and then clear the error message (refer to
Section 8 Troubleshooting
).
To display any recorded error messages, press CLR, FUN, and then
MONTR. The first message will appear. Pressing MONTR again will clear the
present message and display the next error message. Continue pressing
MONTR until all messages have been cleared.
Although error messages can be accessed in any mode, they can be cleared
only in PROGRAM mode.
Preparation for Operation
Section 4-5