Programming Console Operations
Appendix C
338
Operation/Description
Modes*
Key sequence
I/O Table Verify
Used to check that the registered I/O
Table matches the actual
arrangement of I/O Units. Pressing
VER displays the next inconsistency.
R P M
CLR
FUN
SHIFT
*
CH
VER
VER
I/O Table Read
Used to read the I/O Table. The
display gives the Unit type, location,
I/O word allocation, and word
multiplier. Rack and unit numbers will
vary according to the system in use.
By pressing Shift before the arrow
key, the Rack and Unit numbers need
not be specified.
R P M
CLR
FUN
SHIFT
*
CH
MONTR
[Rack no.]
[Unit no.]
MONTR
SHIFT
SHIFT
I/O Table Transfer
Transfers a copy of the I/O Table to
RAM so that the table and and the
user program can be written to
EPROM memory at the same time.
The operation will not work if the
memory is not RAM, or when the
contents exceed 31.7K words.
P
2
With battery check
Without battery check
WRITE
On-line I/O Unit Change
Allows mounting or removal of
permissible Units while the CPU is
operating. Be sure to disconnect the
terminal block before removal and to
reconnect it after mounting.
R P M
EXT
DEL
EXT
INS
[Remove I/O Unit]
[Mount new I/O Unit]
I/O Table Read
in progress
*Modes in which the given instruction is applicable: R = RUN, M = MONITOR, P = PROGRAM