202
Linking to OMRON Controllers
Section 6-1
6.1.2.2
Additional Parameters
6.1.2.2.1
Parameter Maximum Waiting Time for Response
This parameter specifies the maximum time the operating terminal waits for a re-
sponse from the PLC.
The valid range of values is 50 ms to 65535 ms.
The value 500 ms is specified by the programming software by default.
6.1.2.2.2
Parameter Delay until Connection Set-up
This parameter specifies the time the operating terminal waits before starting com-
munication.
The valid range of values is 5 s to 255 s.
The value 5 s is specified by the programming software by default.
6.1.2.2.3
Parameter Monitor Mode
The PLC can be used in the RUN or MONITOR mode of operation.
Write access via the protocol is not possible in the RUN mode.
To be able to edit variables from the terminal, the PLC is switched to the Monitor
mode whenever the operating terminal is booted.
6.1.3
Data Types
The following data types are available for direct user access.
The address ranges depend on the type of PLC.
The valid address ranges are specified below.
Summary of Contents for NT15S
Page 1: ...Cat No V056 E1 1 Programmable Terminal NT4S NT15S NT18S OPERATION MANUAL ...
Page 2: ...ii ...
Page 3: ...iii NT4S NT15S NT18S Programmable Terminal Operation Manual Produced March 1999 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 14: ...xiv ...
Page 26: ...12 The Terminals of the NT Series Section 1 2 1 2 4 1 2 NT4S SF122B E 1 2 4 1 3 NT4S SF123B E ...
Page 37: ...23 The Terminals of the NT Series Section 1 4 1 4 1 3 NT4S SF123B E 1 4 1 4 NT15S SF121B E ...
Page 54: ...40 The Terminals of the NT Series Section 1 7 1 7 6 3 ASCII Character Set Table ...
Page 58: ......
Page 60: ...46 ...
Page 70: ...56 ...
Page 200: ...186 ...
Page 212: ...198 ...
Page 214: ...200 ...