![background image](http://html1.mh-extra.com/html/omron/cs1/cs1_operation-manual_741974052.webp)
3-3
Section
Wiring
32
3. To conform to the EC Low Voltage Directive, use a DC power supply for I/O
that has reinforced or double insulation.
4. When mounting I/O connectors, tighten the connector screws to a torque of
0.2 N
⋅
m.
5. Check that connector wiring has been performed correctly before supplying
power.
6. Do not pull on cables. Doing so may result in disconnection.
7. Do not bend cables beyond their natural limit. Doing so may result in discon-
nection.
Connectors
Connections to the I/O Connector
Connector type
Number of
pins
Ordering as a
set (OMRON)
Ordering individually
(Fujitsu)
Soldered
(See note.)
24 pins
C500-CE241
Socket:
FCN-361J024-AU
Connector cover:
FCN-360C024-J2
Crimp
24 pins
C500-CE242
Housing: FCN-363J024
Connector cover:
FCN-360C024-J2
Contact: FCN-363J-AU
Pressure welded
24 pins
C500-CE243
FCN-367J024-AU/F
Note A soldered connector is provided with the Unit.
Connections to the Special I/O Connector
Connector type
Number of
pins
Ordering as a
set (OMRON)
Ordering individually
(Fujitsu)
Soldered
(See note.)
40 pins
C500-CE404
Socket:
FCN-361J040-AU
Connector cover:
FCN-360C040-J2
Crimp
40 pins
C500-CE405
Socket: FCN-363J040
Connector cover:
FCN-360C040-J2
Contact: FCN-363J-AU
Pressure welded
40 pins
C500-CE403
FCN-367J040-AU
Note A soldered connector is provided with the Unit.
Applicable Connector Terminal Conversion Units
Connecting Cable
Connector–
Terminal
Conversion Unit
Number of pins
Size
XW2Z-
jjj
B
XW2D-40G6
40 pins
Miniature
jjj
XW2B-40G5
Standard
XW2B-40G4
Standard
XW2Z-
jjj
BU
XW2D-40C6
Miniature
The recommended size for cable wires is AWG 24 to 26 (0.2 to 0.13 mm
2
). Use a
cable with an outer diameter of less than 1.61 mm.
Wiring Method
1, 2, 3...
1. Check that all the Units are mounted securely.
Note Ensure that pressure is not exerted on cables.
2. To prevent the wire cuttings that are scattered during wiring from entering
the interior of the Unit, leave the label attached to the top of the Unit when
Recommended Wire Size
Summary of Contents for CS1 -
Page 1: ...Cat No W378 E1 1 Customizable Counter Units SYSMAC CS1 CS1W HI001 HCP22 HCA22 OPERATION MANUAL...
Page 2: ......
Page 3: ...CS1W HIO01 HCP22 HCA22 Customizable Counter Units Operation Manual Produced January 2001...
Page 4: ...iv...
Page 6: ...vi...
Page 10: ......
Page 20: ......
Page 40: ......
Page 60: ......
Page 146: ......
Page 166: ......