Section
Contact I/O Specifications (All Units)
18
2-2
Contact I/O Specifications (All Units)
2-2-1 Contact I/O Specifications
Item
Specifications
Contact
inputs
Number of inputs
12 inputs
•
4 inputs (input bits IR 00000 to IR 00003) can be used either as interrupt inputs or normal
inputs.
Note
Each of these 4 inputs can be set to be used as either interrupt inputs or normal
inputs in the Unit Setup Area (DM 6620). It is also possible to specify the ON, OFF,
or both for the interrupt timing for each point (Input Interrupt Mode or Counter
Mode) in the Unit Setup Area (DM 6620).
•
8 inputs (input bits IR 00004 to IR 00011) can be used as normal inputs only.
Input
voltage/current
24 V
+10%
/
–15%
, 5 mA typical
Min. ON voltage
15.2 V
Max. OFF voltage
4.8 V
Input response
Inputs for interrupt input or normal input (4 points with one common):
ON delay time: 50
µ
s
OFF delay time: 200
µ
s max.
Inputs for normal input (8 points with one common):
ON delay time: 100
µ
s
OFF delay time: 1 ms max.
Circuit
configuration
Interrupt inputs
Normal inputs
Customizable Counter Unit
Internal circuit
Input
indicator
Input
indicator
Internal circuit
4.7 k
Ω
4.7 k
Ω
750
Ω
750
Ω
Summary of Contents for CS1 -
Page 1: ...Cat No W378 E1 1 Customizable Counter Units SYSMAC CS1 CS1W HI001 HCP22 HCA22 OPERATION MANUAL...
Page 2: ......
Page 3: ...CS1W HIO01 HCP22 HCA22 Customizable Counter Units Operation Manual Produced January 2001...
Page 4: ...iv...
Page 6: ...vi...
Page 10: ......
Page 20: ......
Page 40: ......
Page 60: ......
Page 146: ......
Page 166: ......