5-1
Section
Unit Setup Area
60
5-1-3 Details of Special I/O Setup Area
Settings for Pulse Inputs (Enabled at Startup; CS1W-HCP22/HCA22 Only)
Address
Bits
Function
Details
DM 6605
00 to 03
High-speed
counter 1
Pulse input mode
0 Hex: Differential-phase input x1
1 Hex: Differential-phase input x2
2 Hex: Differential-phase input x4
3 Hex: Increment/decrement pulse input
4 Hex: Pulse + direction
04 to 07
Counter reset method
0 Hex: Software reset
1 Hex: Phase Z + software reset
08 to 11
Input pulse frequency
0 Hex: 50 kHz
1 Hex: 200 kHz
12 to 15
Counting mode
0 Hex: Linear counter
1 Hex: Ring counter
DM 6606
00 to 03
Measurement mode specification
0 Hex: No measurement
1 Hex: High-speed counter rate of
change (measurement mode 1)
2 Hex: Frequency measurement
(measurement mode 2)
Note: Frequency measurement is only
possible with counter 1.
04 to 07
PV of high-speed counter
operation at startup
0 Hex: Cleared (The high-speed
counter PV is cleared to 0 at startup or
when the Unit is restart.)
1 Hex: Held (The value of the
high-speed counter that was saved at
power interruption is preset at startup or
when the Unit is restart.)
Note: The timing of power interruption
for the encoder must be considered
when using the present high-speed
counter value saved using this setting.
08 to 15
Sampling time for high-speed
counter rate-of-change
measurement (for measurement
mode 1)
Used to set the sampling time for
high-speed counter rate-of-change
measurement (measurement mode).
00: Scan time
01 to 99 (BCD): 1 to 99 ms (1-ms units)
Note: This setting is valid when the
Measurement Mode Specification (bits
00 to 03 in DM 6606) is set to 1 Hex.
DM 6607
00 to 03
High-speed
2
Pulse input mode
Same as for high-speed counter 1.
04 to 07
g
counter 2
Counter reset method
g
Note: Frequency measurement is not
08 to 11
Input pulse frequency
Note: Frequency me surement is not
possible with high-speed counter 2.
12 to 15
Counting mode
DM 6608
00 to 03
Measurement mode specification
04 to 07
PV of high-speed counter
held/cleared at Startup
08 to 15
Sampling time for high-speed
counter rate of change
measurement (for measurement
mode 1)
DM 6609
00 to 15
Maximum ring
counter value
f
hi h
d
Rightmost 4 digits
Used to set the maximum ring counter
value when the counting mode is set to
i
t
(bit 12 t 15 i DM 6605)
DM 6610
00 to 15
for high-speed
counter 1
Leftmost 4 digits
g
ring counter (bits 12 to 15 in DM 6605).
Range: 0000 0001 to FFFF FFFF Hex
Summary of Contents for CS1 -
Page 1: ...Cat No W378 E1 1 Customizable Counter Units SYSMAC CS1 CS1W HI001 HCP22 HCA22 OPERATION MANUAL...
Page 2: ......
Page 3: ...CS1W HIO01 HCP22 HCA22 Customizable Counter Units Operation Manual Produced January 2001...
Page 4: ...iv...
Page 6: ...vi...
Page 10: ......
Page 20: ......
Page 40: ......
Page 60: ......
Page 146: ......
Page 166: ......