3-2
Section
Installation
24
Indicators
Indicator
Name
Color
Status
Meaning
RUN
Running
Green
Lit
The Unit is operating normally.
g
Not lit
One of the following:
•
The system in the Unit is stopped.
•
The Unit is performing initialization processing.
•
There is a hardware error at the Unit.
•
There is no power supply from the Power Supply Unit.
•
Unit WDT error.
•
Unit recognition error (recognized as CPU Bus Unit)
•
Unit not recognized (The data for this Unit in the registered I/O
table does not correspond with the mounted Unit.)
•
CPU bus error
•
Unit number error
•
Unit RAM error
OPN
Program
i
Green
Lit
The Unit’s program is being executed.
g
execution
Not lit
The Unit’s program is stopped.
ERC
Unit error
Red
Lit
Fatal error at the Unit.
Flashing
A non-fatal error at the Unit, or an error at the CPU Unit.
Not lit
No errors at the Unit.
ERH
CPU Unit error
Red
Lit
An error at the CPU Unit (fatal error, WDT error, monitor error,
or bus error) or an initial setting error in the CPU Unit’s
allocated words in the DM Area.
Not lit
No errors at the CPU Unit.
COMM
Peripheral
i
i
Yellow
Lit
Communications at the peripheral port.
communications
Not lit
No communications at the peripheral port.
IN0 to
IN11
Input signals
Yellow
Lit
Input signal ON
IN11
g
Not lit
Input signal OFF
OUT0 to
OUT7
Output signals
Yellow
Lit
Output signal ON
OUT7
g
Not lit
Output signal OFF
3-2
Installation
3-2-1 Applicable Racks
The Customizable Counter Unit is a CS1-series Special I/O Unit.
•
It can be mounted to a CS1-series CPU Rack or a CS1-series Expansion
Rack.
•
It cannot be mounted to a C200H Expansion Rack or a SYSMAC BUS Slave
Rack.
The number of Units that can be mounted on one Rack (CPU Rack or Expansion
Rack) depends on the maximum supply current of the Power Supply Unit and
the current consumption of the other Units.
Summary of Contents for CS1 -
Page 1: ...Cat No W378 E1 1 Customizable Counter Units SYSMAC CS1 CS1W HI001 HCP22 HCA22 OPERATION MANUAL...
Page 2: ......
Page 3: ...CS1W HIO01 HCP22 HCA22 Customizable Counter Units Operation Manual Produced January 2001...
Page 4: ...iv...
Page 6: ...vi...
Page 10: ......
Page 20: ......
Page 40: ......
Page 60: ......
Page 146: ......
Page 166: ......