3 Part Names and Functions
3-30
CP1E CPU Unit Hardware User’s Manual(W479)
z
Output Specifications for Relay Outputs
(CP1W-8ER/16ER/20EDR1/32ER/40EDR)
•
Estimating the Service Life of Relays
The service life of output contacts is as shown in the following diagram.
•
Restrictions of CP1W-16ER/32ER
Limit the output load current to satisfy the following derating curve.
Item
Specification
Maximum switching capacity
2 A 250 VAC (cos
φ
= 1), 2 A 24 VDC (4 A/common)
Minimum switching capacity
10 mA 5 VDC
Service
life of
relay
Electrical
Resistive
load
150,000 operations (24 VDC)
Inductive
load
100,000 operations (240 VAC, cos
φ
= 0.4)
Mechanical
20,000,000 operations
ON response time
15 ms max.
OFF response time
15 ms max.
Circuit configuration
CP1W-16ER/32ER
COM
OUT
OUT
Output indicator
Internal
circuits
250 VAC, 2A,
24 VDC, 2 A
max.
Contact current (A)
300
200
100
50
30
20
5
3
2
10
0.1
0.2
0.3
0.5
0.7 1
3
5
120-VAC resistive load
24 VDC,
τ
= 7 ms
120 VAC COS
φ
= 0.4
240 VAC COS
φ
= 0.4
24-VDC/240-VAC resistive load
Lif
e (× 10
4
)
Switching frequency: 1,800 operations/hour
2
50
100
55
43
Ambient temperature (˚C)
Output load current(%)