8 Using Expansion Units and Expansion I/O Units
8-16
CP1E CPU Unit Hardware User’s Manual(W479)
0 to 20 mA
The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog current range of 0 to 20 mA.
The entire output range is 0 to 21 mA.
4 to 20 mA
The hexadecimal values 0000 to 1770 (0 to 6000) correspond to an analog current range of 4 to 20 mA.
The entire output range is 3.2 to 20.8 mA.
8-2-4
Flow of Operation
1
•
Connect Analog Output Units.
•
Wire to analog input devices.
2
•
Write range code to output words
CP1W-DA021: Word n+1
CP1W-DA041: Words n+1, n+2
•
Set use of outputs.
•
Select output signals using range codes.
•
Write D/A conversion values to output words
CP1W-DA021: Words n+1, n+2
CP1W-DA041: Words n+1 to n+4
Conversion
Data
Hexadecimal
(Decimal)
0 mA
20 mA
21 mA
189C
(6300)
1770
(6000)
7FFF
8000
0000 (0)
Conversion
Data
Hexadecimal
(Decimal)
4 mA
20 mA
20.8 mA
3.2 mA
189C
(6300)
1770
(6000)
0 mA
7FFF
FED4
(
−
300)
8000
Connect and wire Units.
Create a ladder program.