A-45
Appendices
CP1E CPU Unit Hardware User’s Manual(W479)
A-3 W
irin
g
f
o
r S
e
rial
Co
mm
u
n
icatio
n
s
App
A
-3-3
Con
v
er
ting t
he
Built
-in
RS-23
2
C P
o
rt
t
o
RS
-422A
/485
•
Four-wire Connections
Use one of the following Conversion Units to convert a built-in RS-232C port to an RS-422A port for a
CP1E N/NA
-type CPU Unit.
•
CJ1W-CIF11 RS-422A Conversion Unit
Maximum distance: 50 m, convertible to RS-422A or RS-485.
•
NT-AL001 RS-232C/RS-422A Conversion Unit:
Maximum distance: 500 m, convertible to RS-422A only.
Note
CJ1W-CIF11 cannot be connected to the built-in RS-232C port of the CP1E N
S(1)-type CPU Unit.
The CJ1W-CIF11 RS-422A Conversion Unit is used to convert an RS-232C port to RS-422A/485.
It is directly connected to the built-in RS-232C port of the CP1E N/NA
-type CPU Unit.
The Conversion Unit is not insulated, so the maximum distance for RS-422A/485 is 50 m.
Note
CJ1W-CIF11 cannot be connected to the built-in RS-232C port of the CP1E N
S(1)-type CPU Unit.
z
Appearance
z
Electrical Specifications
•
RS-422A/485 Terminal Block
•
RS-232C Connector
A-3-3
Converting the Built-in RS-232C Port to RS-422A/485
CJ1W-CIF11 RS-422A Conversion Unit
Signal
RDA-
RDB+
SDA-
SDB+
FG
Pin
Signal
1
FG
2
RD
3
SD
4
CS
5
RS
6
+5V
7,8
NC
9
SG(0V)
Hood
NC*
SDA-
SDB+
RDA-
RDB+
FG
3
4
1
2
5
RDA
RDB
SDA
SDB
FG
CP1E N/NA
-type CPU Unit
RS-422A/485 Option Board
Pin
Signal
Signal
Shield
Remote device
Ground the shield at one end
when using CP1W-CIF12.
RDA- RDB+ SDA- SDB+
FG
RDA-
RDB+
SDA-
SDB+
FG
+5V 6
– 7
– 8
SG(0V) 9
1 FG
2 RD
3 SD
4 CS
5 RS
RS-232C port
Connector pin
arrangement