8-31
8 Using Expansion Units and Expansion I/O Units
CP1E CPU Unit Hardware User’s Manual(W479)
8
-3
Ana
log
I/
O
U
n
it
s
8
8-3-4
F
lo
w
o
f O
p
e
rat
ion
2
Wire to analog I/O devices.
(1) Wiring internal circuits of the CPU Unit
(2) Wiring analog output devices to the Analog I/O Unit
(3) Wiring analog input devices to the Analog I/O Unit
Precautions for Correct Use
Precautions for Correct Use
•
Do not connect the shield when using shielded twisted-pair cables.
•
When an input is not being used, short V IN and I IN to COM terminals.
•
Separate wiring from power lines (AC power supply lines, high-voltage lines, etc.)
•
When there is noise in the power supply line, install a noise filter on the input section and the
power supply terminals.
• Analog Inputs
• Analog Outputs
Analog ground
Input 0
Input 1
Analog ground
Output
Internal circuits
510 k
Ω
510 k
Ω
510 k
Ω
510 k
Ω
250
Ω
250
Ω
COM0 (
−
)
V IN0
V IN1
COM1 (
−
)
Internal circuits
COM (
−
)
V OUT
I OUT
AG
NC
NC
I IN0
I IN1
V IN
COM
I IN
V IN
COM
I IN
Analog
device
with
voltage
output
+
−
+
−
Analog
I/O Unit
Analog
device
with
current
output
Analog
I/O Unit
2-core shielded
twisted-pair cable
FG
2-core shielded
twisted-pair cable
FG
FG
FG
V OUT
COM
I OUT
V OUT
COM
I OUT
Analog
device
with
voltage
input
+
−
+
−
Analog
I/O Unit
Analog
device
with
current
input
Analog
I/O Unit
2-core shielded
twisted-pair cable
2-core shielded
twisted-pair cable
Summary of Contents for CP1E-E10DT-A
Page 3: ......
Page 31: ...26 CP1E CPU Unit Hardware User s Manual W479...
Page 273: ...Index 4 CP1E CPU Unit Hardware User s Manual W479...
Page 275: ...Revision 2 CP1E CPU Unit Hardware User s Manual W479...
Page 276: ......