5 Installation and Wiring
5-8
CP1E CPU Unit Hardware User’s Manual(W479)
z
Installation Height
The installation height is approximately 90 mm.
When a cable is connected to an Option Board, however, the additional height must be included.
Always allow for the additional height when considering the depth of the control panel in which the
PLC is to be mounted.
There are two installation methods.
z
DIN Track Installation
•
Units can be mounted to PEP-50N (50 cm) or PEP-100N/100N2 (100 cm) DIN Tracks.
•
Units can be moved and removed easily.
•
The installation height in the control panel will be increased depending on the type of DIN tracks
used.
z
Surface Installation
Units can be directly mounted in the control panel using M4 screws.
z
DIN Track Installation
Secure the DIN Track with screws in at least three places.
z
Surface Installation
A CP1E CPU Unit and CP-series Expansion I/O Units and Expansion Units can be mounted using
M4 screws. For restrictions on the number of Expansion I/O Units and Expansion Units that can be
connected, refer to 2-3 Expansion I/O Unit or Expansion Unit.
1
Use a screwdriver to pull down the DIN Track mounting pins from the back of the Units to
release them, and mount the Units to the DIN Track.
Installation Methods
Installation Example
DIN Track Installation
DIN Track
Secure with screws
Release
DIN Track mounting pins