6-13
6 Troubleshooting
CP1E CPU Unit Hardware User’s Manual(W479)
6
-1
T
roub
le
s
hoot
ing CPU U
n
it
Er
ror
s
6
6-1-10
N
on-f
a
ta
l E
rrors
z
Reference
z
Reference
z
Reference
z
Reference
Error flag
Backup Memory Error Flag, A315.15
Error code (A400)
00F1
Error information
−
PLC Setup Errors
Cause
Remedy
A set value error occurred in the PLC Setup.
Correct the PLC Setup with correct values.
Error flag
PLC Setup Error Flag, A402.10
Error code (A400)
009B
Error information
−
Option Board Errors (Only for N/NA
-type CPU Units)
Cause
Remedy
The Option Board is removed while the power is
being supplied.
(A315.13 will turn ON.)
Turn OFF the power supply and then install the Option
Board again.
Error flag
Option Board Error Flag, A315.13
Other Non-fatal Error Flag, A402.00
Error code (A400)
00D1
Error information
−
Battery Errors
Cause
Remedy
If the PLC Setup is set to detect battery errors, this
error will occur when there is an error in the battery
in the CPU Unit (i.e., the voltage is low or a battery
is not mounted).
Check the battery connections.
Select the Do not detect battery error Check Box in the
PLC Setup setting if battery-free operation is being used.
Error flag
Battery Error Flag, A402.04
Error code (A400)
00F7
Error information
−