3 Part Names and Functions
3-18
CP1E CPU Unit Hardware User’s Manual(W479)
The NA-type CPU Units of the CP1E CPU Units are equipped with 2 built-in analog inputs and 1
built-in analog output.
z
Analog Input Specifications
z
Analog Output Specifications
* When the analog current output is 0 to 20mA, the accuracy cannot be ensured at 0.2mA or less.
z
Shared I/O Specifications
Analog I/O (NA-type CPU Units)
Item
Voltage input
Current input
Number of inputs
2 inputs (Allocated 2 words: CIO 90 to CIO 91.)
Input signal range
0 to 5 V, 1 to 5 V, 0 to 10 V, or -10
to 10 V
0 to 20 mA or 4 to 20 mA
Max. rated input
±15 V
±30 mA
External input impedance
1 M
Ω
min.
Approx. 250
Ω
Resolution 1/6000
Overall accuracy
At 25°C
±0.3% full scale
±0.4% full scale
0 to 55°C
±0.6% full scale
±0.8% full scale
A/D conversion
data
-10 to 10 V
F448 to 0BB8 hex FS
Other ranges
0000 to 1770 hex FS
Averaging function
Supported (Set for individual inputs in the PLC Setup.)
Open-circuit detection function
Supported (Value when disconnected: 8000 hex)
Item
Voltage output
Current output
Number of outputs
1 output (Allocated 1 word: CIO 190.)
Output signal range
0 to 5 V, 1 to 5 V, 0 to 10 V, or -10
to 10 V
0 to 20 mA* or 4 to 20 mA
Allowable external output load resis-
tance
1 k
Ω
min.
600
Ω
max.
External input impedance
0.5
Ω
max.
---
Resolution 1/6000
Overall accuracy
At 25°C
±0.4% full scale
0 to 55°C
±0.8% full scale
D/A conversion
data
-10 to 10 V
F448 to 0BB8 hex FS
Other ranges
0000 to 1770 hex FS
Item
Specification
Conversion time
2 ms/point (6 ms total for 2 analog inputs and 1 analog output.)
Isolation method
Photocoupler isolation between analog I/O terminals and internal circuits. No
isolation between analog I/O signals.