6 Troubleshooting
6-12
CP1E CPU Unit Hardware User’s Manual(W479)
A non-fatal error has occurred if both the RUN indicator is lit and the ERR/ALM indicator is flashing
during operation (i.e., in RUN or MONITOR mode).
z
CPU Unit Indicators
: Not lit
: Flashing
: Lit
Information on the non-fatal errors can be obtained from the Errors Tab Page of the CX-Program-
mer’s PLC Errors Window.
Take corrective actions after checking error details using the display messages and the Auxiliary
Area Error Flags and error information.
•
Errors are listed in order with the most serious errors first.
•
If two or more errors occur at the same time, the most serious error code will be stored in A400.
z
Reference
6-1-10 Non-fatal Errors
Errors Created with FAL Instructions
Cause
Remedy
A FAL instruction was executed in the program to
create a non-fatal error.
(The executed FAL number 001 to 511 will be stored
in A360 to A391. The number 4 will be added to the
front of 101 to 2FF (which correspond to executed
FAL numbers 001 to 511) and the result will be
stored in A400 as error code 4101 to 42FF. )
Check the conditions for executing FAL instructions and
remove any causes of the user-defined error.
Error flag
FAL Error Flag, A402.15
Error code (A400)
4101 to 42FF
Error information
−
Backup Memory Error
Cause
Remedy
Writing to the backup memory (built-in EEPROM)
fails.
(A315.15 will turn ON. )
Replace the CPU Unit when the backup memory (built-in
EEPROM) has been written to more than 100,000 times.
POWER
RUN
INH
PRPHL
BKUP
ERR/AL
—: Irrelevant
POWER
RUN
ERR/ALM
INH
PRPHL
BKUP
—
—
—