2-15
2 Basic System Configuration and Devices
CP1E CPU Unit Hardware User’s Manual(W479)
2
-3
Ex
p
a
ns
io
n
I/O
Uni
t or
Ex
p
a
ns
io
n
Uni
t
2
2-1-2
Bas
ic S
yst
em
Conf
igur
at
ion Us
in
g
an
N/
NA
(S
)-t
y
pe C
P
U
Unit
The following restrictions apply to the CP-series Expansion Units and CP-series Expansion I/O Units
that can be connected to CP1E CPU Units.
A total of up to three Expansion Units and Expansion I/O Units can be connected to an E30/40/60(S),
N30/40/60(S ) or NA20 CPU Unit. Expansion Units and Expansion I/O Units cannot be connected to
E10/14/20(S) or N14/20 CPU Units.
Each CPU Unit can connect one device to pin 6 (+5V power supply) of the CP1W-CIF01 built-in
RS232C port. If one CPU Unit connects two devices, a total of up to two Expansion Units can be con-
nected to the CPU Unit.
The following restrictions apply when using the CPU Unit’s external power supply.
AC-power-supply E30/40/60(S), N30/40/60(S ) or NA20 CPU Unit
The power supply capacity is restricted for AC-power-supply E30/40/60(S), N30/40/60(S ) or NA20
CPU Units. It may not be possible to use the full 300 mA of the external power supply, though a CPU
Unit can connect any CP-series Expansion I/O Unit or Expansion Unit.
The entire 300 mA from the external power supply can be used if Expansion Units and Expansion
I/O Units are not connected.
Refer to
2-4-1 External Power Supply Capacity When Expansion I/O Units or Expansion Units are
Connected
for details.
AC-power-supply or DC-power-supply E10/14/20(S), N14/20 CPU Unit
There is no external power supply on AC-power-supply or DC-power-supply E10/14/20(S), N14/20
CPU Units.
According to the ambient temperature, there are restrictions on power supply voltage and output
load current for the DC-power-supply CPU Units.
Refer to
Output Specifications for Relay Outputs
in
3-1-3 Common I/O Specifications
and in
3-2-4 I/O
Specifications
for details.
Use CP1W-32ER/ET/ET1 32-point Output Units with the number of simultaneously ON less than 24
points (75%).
2-3-5
Restrictions on System Configuration
Restriction on the Number of Connected Units
Restrictions on External Power Supply Capacity
Restrictions by ambient temperature
Restrictions on the Number of Simultaneously ON Points
Summary of Contents for CP1E-E10DT-A
Page 3: ......
Page 31: ...26 CP1E CPU Unit Hardware User s Manual W479...
Page 273: ...Index 4 CP1E CPU Unit Hardware User s Manual W479...
Page 275: ...Revision 2 CP1E CPU Unit Hardware User s Manual W479...