![background image](http://html.mh-extra.com/html/omron/cj1w-pnt21/cj1w-pnt21_operation-manuals_742351180.webp)
7-15
7 Troubleshooting and Maintenance
CJ-series PROFINET IO Controller Unit Operation Manual for NJ-series CPU Unit (W511)
7-3 Even
t L
ogs
7
7-3
-2 Err
or T
able
Event code
Event name
Meaning
Assumed cause
Level
Maj Prt Min Obs Info
18010000
Local parameter
storage error
The setup data in
non-volatile mem-
ory may be cor-
rupted.
•
An error occurred during the storage of
the data transferred from the configura-
tion software to the Unit’s internal non-
volatile memory.
X
18020000
Local parameter
load error
The Unit cannot
load the internally
stored configura-
tion and setup data.
•
The internally stored configuration and
setup data is corrupted or erased.
X
18030000
File read error
The unit cannot
load the configura-
tion and setup data
stored on the mem-
ory card.
*Limited memory
card functionality
based on CPU ver-
sion. Check specifi-
cation details for
more information.
•
An error in the file or and error during
transfer.
X
18040000
Error log storage
error
The Error Log data
in the non-volatile
memory may be
corrupted.
•
An error occurred during an attempt to
write the error log to internal non-volatile
memory.
•
Upon restart, the Unit will re-initialise the
Error Log.
X
38080000
Invalid configuration The Unit has not
been configured
correctly.
•
The Configuration data is incorrect.
•
The Unit cannot parameterize the allo-
cated IO Devices and cannot begin
exchanging data.
X
38090000
Configuration error
One or more config-
uration errors have
been detected.
•
An error has been detected in the con-
tents of the Configuration set.
X
88010000
Controller is in
OFFLINE mode
The Unit is currently
not in ONLINE
mode.
•
The Unit is not capable of communicating
on the network.
•
Hardware errors occurred during startup
or normal operation.
X
88020000
Link status
No Ethernet con-
nection could be
established.
•
There is no Ethernet cable connected.
•
A link could not be established with an IO
Device, switch or other Ethernet device.
X
88030000
Hardware error
Hardware errors
have occurred.
•
An error has occurred in the bus or
accessing data to the Unit.
X