5 Operation
5-6
CJ-series PROFINET IO Controller Unit Operation Manual for NJ-series CPU Unit (W511)
• Signal
will let the indicators of the selected device flash for 3 seconds. This is useful to physically
find the device in the installation. When found the device can get a logical name.
• Set IP Address...
will set the IP Address of the selected device. The IP Address can be fixed or
temporary. But finally the IO Controller will over write the IP address when it establishes a connec-
tion to the IO Device. However a temporary IP Address can come in handy when uploading or
downloading SmartSlice configurations with the GRT1-PNT PROFINET IO Device DTM when no
IO Controller is available.
• Set Device Name...
IO Devices needs to have a name. This is the only way a IO Controller can
find an IO Device on the network. This same Device Name must be entered in the IO Controllers
configuration.
• Reset to factory defaults...
Resets the device to its factory defaults like default name and IP-
address 0.0.0.0.
Precautions for Correct Use
Precautions for Correct Use
Setting a Device Name for an IO Device is the first action that must be done. If there is no match
between the Device Name in the IO Device and what is in the configuration in the IO Controller
then the IO Device will never been found by the IO Controller.