7 Troubleshooting and Maintenance
CJ-series PROFINET IO Controller Unit Operation Manual for NJ-series CPU Unit (W511)
7-3 Even
t L
ogs
7
7-3
-3 Err
or D
escriptions
Event name
Configuration Error
Event code
38090000 hex
Meaning
One or more configuration errors have been detected.
Source
Function Module
Source details
CJ-series Unit
Detection
timing
At power ON or
reset.
Error attributes
Level
Minor
Recovery
Error reset
Log category
System
Effects
User program
Continues
Operation
Cannot exchange data with IO Devices until a valid Con-
figuration set is restored.
System-defined
variables
Variable
Data type
Name
*_CfgErr
BOOL
Configuration Error
Cause and cor-
rection
Assumed cause
Correction
Prevention
An invalid configuration has been
transferred to the Unit.
Correct the configuration in CX-Con-
figuratorFDT and download again to
the Unit.
Do not transfer invalid configurations
to the Unit.
Attached
information
None
Precautions/
Remarks
None
Event name
Controller is in OFFLINE mode
Event code
88010000 hex
Meaning
The Unit is currently not in ONLINE mode.
Source
Function Module
Source details
CJ-series Unit
Detection
timing
Continuously
Error attributes
Level
Minor
Recovery
Error reset
Log category
System
Effects
User program
Continues
Operation
The Unit is in OFFLINE mode and is not capable of com-
municating on the network possibly caused by hardware
errors occurring during startup or normal operation.
System-defined
variables
Variable
Data type
Name
*_OfflineSta
BOOL
Controller is in OFFLINE mode
Cause and cor-
rection
Assumed cause
Correction
Prevention
The User or program has changed
the operating mode of the Unit to
OFFLINE.
A hardware error is preventing the
Unit from going ONLINE.
Change the mode to ONLINE. If the
unit cannot go ONLINE, determine
the cause by checking other errors
and/or device variable status.
Check user program, hardware or
other possible causes of mode
change.
Attached
information
None
Precautions/
Remarks
None
Event name
Link Status
Event code
88020000 hex
Meaning
No Ethernet connection could be established.
Source
Function Module
Source details
CJ-series Unit
Detection
timing
Continuously
Error attributes
Level
Minor
Recovery
Automatic
Log category
System
Effects
User program
Continues
Operation
Set ON by the Unit if there is no Ethernet cable connected
to the port of the IO Controller or a link could not be
successfully created to an IO Device, switch or other
Ethernet device. If the unit cannot establish a link with
another device at 100Mbps full-duplex then this bit will be
set.
System-defined
variables
Variable
Data type
Name
*_LinkSta
BOOL
Link Status