9 Troubleshooting and Maintenance
9-30
CJ-series DeviceNet Units Operation Manual for NJ-series CPU Unit(W497)
0101
Transmission failed because the local node is
not participating in the network.
Explicit message communications command:
Bit 15: OFF
Bits 14 to 8: 0
Bit 7: ON
Bits 6 to 0: Node address of command source
Explicit message communications response:
Bit 15: ON
Bits 14 to 8: 0
Bit 7: ON
Bits 6 to 0: Node address of command source
No
0105
Transmission failed because of a node address
setting error.
0106
Transmission failed because of a node address
duplication error.
0107
Transmission failed because the other node is
not participating in the network.
0108
Transmission failed because there is no Unit
with the specified unit number.
0109
Transmission failed because the other node is
busy.
010B
Transmission failed because of a CPU Unit
error. Frame discarded due to one of the fol-
lowing:
• A cyclic service monitoring timeout occurred.
• A CPU Unit watchdog timer error occurred.
• Another CPU Unit error occurred.
010D
Transmission failed because the destination
address is not registered in the routing table.
010E
Transmission failed because the routing table
has not been registered.
010F
Transmission failed because of a routing table
error.
0110
Transmission failed because of too many repe-
titions.
0111
Transmission failed because the command
exceeded the max. command length.
0112
Transmission failed because of a header error.
0117
Packet discarded because the internal recep-
tion buffer is full.
0118
Illegal packet discarded.
0120
Unexpected routing error
0123
Packet discarded because the internal trans-
mission buffer is full.
0124
Routing failed because maximum frame length
was exceeded.
0125
Packet discarded because of response time-
out.
021A
Setting table logic error
00 Hex
03 Hex: Routing table
0A Hex: Master scan list
0B Hex: Slave scan list
0C Hex: Message moni-
toring timer list
0D Hex: Scan time
Yes
0211
Node address duplication (cause)
00 Hex
Local node address
No
0300
Packet discarded because of parameter error.
Same as the code (such as 0101 Hex) in the dis-
carded explicit message packet.
No
0340
Bus Off detected
00 Hex
00 Hex
No
0341
Network power supply error
00 Hex
00 Hex
No
0342
Transmission timeout
00 Hex
00 Hex
No
Error
code
(Hex)
Error
Detail code
Record
stored in
EEPROM
First byte
Second byte