9-37
9 Troubleshooting and Maintenance
CJ-series DeviceNet Units Operation Manual for NJ-series CPU Unit(W497)
9-4 Even
t L
ogs
9
9-4-2 Error T
a
b
le
34BD 0000 hex
Verification
Error
The slave informa-
tion registered in
the scan list does
not agree with the
actual slave infor-
mation.
•
A slave that is in the scan list
does not exist.
•
The node address of the local
Unit, which is the master, is reg-
istered in the scan list.
•
If the system is set to check the
vendor in the detailed verifica-
tion settings, the vendor of the
slave does not match the regis-
tration in the scan list.
•
If the connection path is set in
the detailed verification set-
tings, then setting the connec-
tion path that is set in the scan
list failed.
•
The size of the slave I/O data
does not match the registration
in the scan list.
•
If the device type is set in the
detailed verification settings,
then setting the device type that
is set in the scan list failed.
•
If the product code is set in the
detailed verification settings,
then setting the product code
that is set in the scan list failed.
•
The device does not support
the I/O service specified in the
scan list.
S
34BE 0000 hex
Structure
Error
The scan list is dis-
abled and an error
occurred that pre-
vented making I/O
allocations.
•
The I/O words allocated to
slave overlap.
•
The I/O words allocated to the
slave exceed the valid range.
•
The I/O size of the slave
exceeds 200 bytes for outputs
or 200 bytes for inputs.
S
34BF 0000 hex
Master I/O
Refresh Error
The I/O memory in
the destination
CPU Unit for I/O
refreshing could not
be found when
refreshing the mas-
ter function data in
the CPU Unit.
•
I/O words are allocated in an
EM bank that does not exist.
S
34C0 0000 hex
Master User-
set Alloca-
tions User
Setting Failed
An error occurred in
the following opera-
tion for user alloca-
tion of the master.
•
The master function is not
enabled.
•
There is a mistake in the user
allocations in the master.
•
CPU Unit is not in PROGRAM
mode.
•
More than one software switch
changed to TRUE at the same
time. Or, another software
switch changed to TRUE before
processing was completed for a
previous software switch.
S
34C1 0000 hex
Communica-
tions Cycle
Time Setting
Failed
An error occurred in
one of the following
operations when
setting the commu-
nications cycle
time.
•
There is an error in the set
information.
•
CPU Unit is not in PROGRAM
mode.
S
Event code
Event name
Meaning
Assumed cause
Level
Reference
Maj
Prt
Min
Obs
Info
Summary of Contents for CJ1W-DRM21
Page 12: ...Manual Structure 10 CJ series DeviceNet Units Operation Manual for NJ series CPU Unit W497 ...
Page 42: ...Revision History 40 CJ series DeviceNet Units Operation Manual for NJ series CPU Unit W497 ...
Page 345: ...Index 1 CJ series DeviceNet Units Operation Manual for NJ series CPU Unit W497 I Index ...
Page 349: ......